Page 494 - Industrial Power Engineering and Applications Handbook
P. 494

15/468 Industrial Power Engineering and Applications Handbook
        will be maintained within the prescribed limits. Figure   transformer 41 511 10 V.
        15.10 illustrates  this  requirement  and  Example  15.1   The following data have been assumed:
        demonstrates the procedure to determine the required VA   System: 415 V,  three-phase, four wire.
        of a control transformer.
                                                       Control voltage:  11  0 V  a.c.
        Example 15.1                                   Control wire: 2.5 mm2 (resistance of wire = 7.6 Q/lOOO  m, as
        Consider  the  control  scheme of  an  auto-control  capacitor   in Table 13.15).
        panel  as  shown  in  Figure  23.37.  The  scheme shows  the
        control voltage  as being tapped from the  main bus. But for   Approximate  length of  wire for each feeder up to the power
        our  purpose,  we  have  considered  it  through  a  control   factor correction relay (PFCR): 35 m.

        (1) A study of the control scheme

        Component             Total quantity nos   Maximum hold-on occurs when   Maximum inrush occurs whenfive steps of
                                               all the six steps of the PFCR   the PFCR are ON and the sixth is
                                              are ON                  switched  ON

                                                                      Hold on            Inrush
        Main contactor 125 A   6               6                      5                   1
        Auxiliary  contactor 6 A   2           1 (auto or manual)      1                 -
        On indicating  light   8               6 (auto or manual)     5                   1
        PFCR                  1                1 (6 steps)            5                   1
                                             -                        ~                  -
        (2) Approximate VA  burden and cos f$ for each component, as available from the manufacturers’ catalogues

        Componenr                    VA               cos @            W = VA cos @    VAr = VA sin @
        125 A contactor
                     Hold-on          65              0.3 I            20.15           61.79
                     Inrush          900              0.42             378             817
        6A contactor
                     Hold-on          15              0.33              4.95           14.16
                     Inrush          115              0.60             69              92
        Indicating  light
                      Hold-on          7              I                 7              -
                      Inrush           7              1                 7              ~
        PFCR  (each step)a
                      H o 1 d - o n    5              1                 5              -
        aPFCRs are available  in both  static  and electromagnetic versions. Their VA  levels  therefore  vary  significantly  due to inbuilt  switching
        relays, LEDs (light emitting diodes) and p.f. meter etc. For illustration  we have Considered an average VA  burden of 5VA at unity p.f. for
        each step. For static relays, this may be too low
        (3) Computing the maximum hold-on (steady state) and inrush burden values and their cos f$
                                                  1
                         Maximum hold-on values    Maximum pick-up (inrush) values
                                                   Hold-on for five steps already ON   1   Inrush for the sixth step
        Component        Qty    Total     Total    Qty     Total    Total       Qty   ,   Total  ,  Total
                                W         VA r             W        VA r             I  W    VAr

        Main contactor   6      6 x 20.15   6 x61.79   5   5 x 20.15   5 x 61.79   1   378   817
                                = 120.90   = 370.74        = 100.75   = 308.95
        Auxiliary  contactor   1   4.95   14.16     I      4.95     14.16       -      -     -
        Indicating light   6    6~7=42  -          5       5x7=35   -           1      7     -
        PFCR (steps)     6      6X5=30    -        5       5X5=25   -           1      5     -

        Total                    197.85   384.90           165.70 (a)  ,  323.11(b)   ~   1   390(cj 1  817(d)
                       :.   VA = J197.852 + 384.90’                :.  Total inrush, W = 555.7 ( a + c)
                                                                     and VAr    = 1140.11 (b + d)
                           = 433 without considering the           :.  VA      = 4555.7’  + 1140.11’
                             burden for wire leads                             = 1268 without considering
                                                                                 the burden for wire leads
   489   490   491   492   493   494   495   496   497   498   499