Page 498 - Industrial Power Engineering and Applications Handbook
        P. 498
     15/472  Industrial Power Engineering and Applications Handbook
                     (a) Single-phase HT CT
                                                              11 kVCT                33 kV CT
                                                       Figure 15.15(a)  Typical  outdoor-type  oil-filled  bar  primary  or
                                                       wound primary HV CTs  (Courtesy: Kappa Electricals)
                      (b) Three-phase LT CT
        Figure 15.14  Typical indoor-type bar primary epoxy resin
        cast CTs (Courtesy: Kappa Electricals)
        circuit (the impedance of all the devices connected to it),
        expressed in ohms and power-factor or volt-amperes, at
        the rated  secondary  current.  The CTs will  be  selected
        nearest to the computed total VA burden in the circuit. A
        CT with a higher VA burden than connected will have a
        slightly higher error besides size. A slightly less VA rating
        than the connected may normally be permissible, subject
        to  confirmation  by  the  manufacturer.  Typical  values
        of  VA  burdens  at the rated current for the devices that
        a  measuring  CT  may  have  to  usually  feed  are  as
        follows:
        Instruments and measuring devices*
        Moving iron ammeters            1.5 to 5 VA    Figure 15.1  5(b)  400 kV bar primary outdoor current transformer
        Recording ammeters              2 to 10 VA     (Courtesy: BHEL)
        Current coils of watt-meters    5 VA
        Recording watt-meters           5 VA
        kWh and kVAr meters             5 VA
        Thermal demand ammeters         3 VA           *These values are typically for moving iron instruments and devices.
        Thermal maximum demand ammeters   4 to 8 VA    For electronic instruments and devices they would be of the order
        Power factor (p.f.) meters      5 VA           of 0.1 to 0.5 VA.





