Page 503 - Industrial Power Engineering and Applications Handbook
P. 503

Instrument and control transformers: application and selection  15/477
           Any main CT that is underloaded will also add to the   measuring CT, a protection CT will have a high saturation
         error in the measurement. Similarly, if provision is made   level  to  allow  the  high  primary  current  to  transform
         in  the  primary  of  the  summation CT to  accommodate   substantially to  the  secondary  as  may  be  required,
         future circuits  but  is  not  being  utilized  it  must  be  left   depending upon  the current setting of the protective or
         open. otherwise it will also add to the error. The impedance   tripping relays. For protection CTs, therefore, the accuracy
         of  the  shorting terminals  will  add to the impedance of   class is of little relevance up to the primary rated current,
         the circuit and will  increase the total error.   but a true reflection in the secondary is more important
           As  the  currents  of  each  circuit  are  summed  by  the   of a fault condition in the primary.
         summation CT. the VA  burden of each main  CT is also
         borne by  the summation CT in addition to its own. The   Corollary
         VA  level  of  the  summation  CT,  including  its  own, is
         shared proportionately by all the main CTs in the ratio of   Both requirements  of  measuring  and  protection  cannot
         their  primary  currents. Referring to the  three  different   be met through one transformer generally. Thus two sets
         circuits of Figure 15.2 1 (b), having the ratings as shown   of transformers are required for a power circuit associated
         in  Table  15.10, the rating of the summation CT can be   with a protection scheme, one for measurement and the
         chosen as 340011 A. If we choose a VA level of this CT   other for protection.
         as 25 VA, making no provision for the future, then the
         VA burden shared by each main CT will be as calculated   (i) Accuracy limit primary current
         in the last column, ignoring the losses in the connecting
         leads. Based on this, the VA burden of each main CT can   This is the highest limit of the primary current that can
         be decided.                                   be transformed to the secondary, substantially proportional,
                                                       complying with the requirement of the composite error
                                                        (Section 15.6.1). For example. a protection CT 2000/SA
         15.6.5  Protection current transformers       represented as 5P10 means that a primary current up to
         These are employed to detect a fault, rather than measuring   ten times the rated (Le. up to 2000 x 10 A) will induce a
         the current of a power system or the connected equipment.   proportional secondary current. The factor  10 is known
         There is a fundamental difference in the requirement of   as the accuracy limit factor as noted below.
         a  measuring  and  a  protective  transformer  in  terms  of
         accuracy.  saturation  level  and  VA  burden.  Unlike  a   (ii) Accuracy limit factor (ALF)
                                                       This is the ratio of the rated accuracy limit primary current
                     Main CTs                          to the rated primary current. For example, in the above
                        P                              case it is
                       I\
          R  Y  B     ,I'   \
                       ,(
                                                        2000 x  10  -
                                                                 -
                                                          2000
                                                   B.   The standard prescribed factors can be one of 5. IO,  15.
                                                        20 and 30.
                                      Summation CT     (iii) Accuracy class
                                                       This defines the maximum permissible composite error
                                                       at the rated accuracy limit primary current, followed by
            (a) Measuring the sum load of three circuits on phase B.   letter P for protection. The standard prescribed accuracy

                                                Main CTs
                                                                                      Rl
                                                                                      Yl
                                                                                      Bi

                                                                                      R2
                                                                                      y2
                                                                                      82
                                      r"""""""l  T""""""""i  a-
                                                                                    Summation
                                                         Burden
                                          Burden
                                                                                    cTs
                                                                        Burden
                           (b) Measuring the sum load of two circuits connected on different supply sources.
                                      Figure 15.21  Application of  summation CTs
   498   499   500   501   502   503   504   505   506   507   508