Page 504 - Industrial Power Engineering and Applications Handbook
P. 504

15/478  Industrial Power Engineering and Applications Handbook
        Table 15.10                                    Example 15.3
                                                       Consider a protective scheme having a total VA burden of 15
                                                       and requiring an accuracy limit factor (ALF) of  20:
        Circuit whose   Current rating  Main CT   VA burden shared
        current is being       ratio    by the main    :.  VA  x ALF = 15 x 20 = 300
        summed                          CTs
                                                       which is too large to design a CT adequately. In such cases
                                                       it  is advisable to  consider  two sets  of  CTs,  one  for those
        Circuit 1   1000 A     1000/1 A   *25  'Oo0    relays that  are  set  high  and  operate  at  high  to  very  high
                                           3400
                                        = 7.0 VA       currents (short-circuit protection relays) and the second for
                                                       all other  relays that  are  required to  operate  on  moderate
         Circuit 2   800 A     800/1 A   *25           overloads. For example, consider one set of  CTs for short-
                                           3400        circuit protection having
                                           =  6.0 VA
        Circuit 3   1600 A     1600/1 A   *25  l6Oo         VA  = 5
                                           3400
                                         =  12.0 VA    and  ALF=20
                    Total load   Ratio of   *VA of     i.e. a 5P20 CT having a product of VA x ALF of not more than
                    = 3400 A   summation   summation   150 and the other set for all the remaining protections having,
                               CTs = 3400/1  CTs = 25
                                                       say,
                                                            VA  = 10
         classes may be one of 5P, 10P and 15P. A protection CT   and  ALF = 5
         is designated by accuracy class, followed by  accuracy
         limit factor, such as 5P10. The current error, phase error   i.e. a 10P5 CT having a product of  VA  x ALF of  much less
         6 (Figure 15.18) and the composite error with the rated   than 150.
         burden  in the circuit are as in Table  15.9, according to
         IEC 60044-1. It should be chosen depending upon the   Note
         protective  device  and  its  accuracy  requirement  to   For  high  set  protective  schemes,  where  to  operate  the
         discriminate.  Closer  discrimination  will  require  more   protective relays, the primary fault currents are likely to  be
                                                       extremely high, as in the above case. Here it is advisable to
         accurate CTs.                                 consider  a  higher  primary  current  than  the  rated for  the
                                                       protection CTs  and thus  indirectly reduce the ALF and the
         Note                                          product of VA x  ALF.  In some cases, by doing so, even one
         An accuracy class beyond  1OP is generally not recommended.   set of CTs may meet the protective scheme requirement.
         (iv) Output and accuracy limit factors        Example 15.4
                                                       Consider a system being fed through a transformer of  1500
         The capabilities of a protection CT are determined by the   kVA, 11/0.433 kV, having a rated LV current of 2000 A. The
         primary inputs of a CT such as the primary ampere turns   protection CT ratio on the LV side for the high set relay may
         AT  (primary  current x primary  number of  turns), core   be considered as 4000/5 A (depending upon the setting of
         dimensions  and the  quality  of  laminations.  All  this  is   the relay) rather than a conventional 2000/5 A, thus reducing
         roughly proportional  to the product of the rated output   the ALF of the previous example from 20 to 10. Now only one
         (VA) and the rated accuracy limit factor of the CT. For   set  of  15 P10 CTs  will  suffice,  to  feed the total  protective
                                                       scheme and have a VA  x  ALF of  not more than 150.
         normal use, the product of the VA burden and the accuracy
         limit factor of a protection  CT should not exceed  150,
         otherwise it  may  require  an  unduly  large  and  more   Other considerations when selecting a
         expensive CT. For example, for a 10 VA. CT, the accuracy   protection CT
         limit  factor should not exceed  15 and vice  versa. The
         burden and the accuracy limit factor are thus interrelated.   1 The accuracy limit factor (ALF) will depend upon the
         A  decrease  in  burden  will  automatically  increase  its   highest setting of thc protective device. For a 5 to  10
         accuracy  limit  factor and vice  versa.  In  a  ring  or bar   times setting of the high set relay, the ALF will be a
         primary CT, which has only one turn in the primary, the   minimum of  10.
         ampere turns are limited by the primary current only, thus   2  A  higher  ALF  than  necessary  will  serve  no  useful
         limiting the accuracy and burden of such CTs. This is one   purpose.
         reason why CTs of up to 5OAare generally manufactured   3 It has been found that, except high set relays, all other
         in  a  wound  primary  design,  with  a  few  turns  on  the   relays may not require the ALF to be more than 5. In
         primary  side to  obtain a reasonably  high  value  of  VA   such cases it is worth while to use two sets of protection
         burden and accuracy. For larger products than  150, it is   CTs, one exclusively  for high  set relays, requiring  a
         advisable to use more than one protection CT, or use low   high accuracy limit factor (ALF), and the other, with
         secondary current CTs, i.e.  1 A instead of 5 A.   a lower ALF, for the remaining relays. Otherwise choose
                                                         a higher primary  current than rated,  if  possible,  and
                                                         indirectly  reduce  the ALF  as illustrated  in  Example
         Note
         For similar reasons, a measuring CT of up to 50 A primary current   15.4 and meet  the  requirement  with just  one set  of
         is recommended to be produced  in a wound design.   protection CTs.
   499   500   501   502   503   504   505   506   507   508   509