Page 499 - Industrial Power Engineering and Applications Handbook
P. 499

istrument and control transformers: application and selection  15/473

                                                      VA = 52 x        [l + 3.93 x 10"  (90-20)]
                                                                 1000
                                                         = 2.42 VA      (for details refer to Table 14.4)

                                                      Computing the VA burden
                                                      1  The VA  values  of  some of  the devices used  in the
                                                        circuit may be available at a different current rating
                                                        from the  actual  rated  secondary  current  (1 or  5 A)
                                                        chosen for the CT circuit. To compute the VA burden
                                                        of a circuit when selecting the correct VA level of a
                                                        CT, the VA values of all the devices not corresponding
                    (a) Single phase HT CT              to the rated current of the circuit must be first converted
                                                        to  the  rated  current  and  only  then  added.  This  is
                                                        essential because  the VA  level  of  a CT varies  in  a
                                                        square proportion  of the current passing  through  it,
                                                        Le., VA = 12. As a result, at lower operating currents
                                                        its VA capacity to feed a circuit would also decrease
                                                        sharply while the VA requirement of the instruments
                                                        or the relays connected in the circuit will remain the
                                                        same. It is therefore important that the VA level of the
                                                        CT is raised in the same inverse square proportion of
                                                        the current to maintain at least the same level of VA
                                                        to  make  it  suitable  to  activate  the  measuring  or
                                                        protective devices connected in the circuit, i.e.




          (b) HT epoxy resin cast   (c) HT epoxy resin cast   where VA, and VA2 are the VA levels of  a circuit at
                                                        currents I, and Z2 respectively.

                                                      Example  15. 2
                                                      Consider a 5 A secondary CT circuit connected to the following
                                                      devices:
                                                      Device I  = 0.3 VA at 1 A
                                                      Device II  = 5 VA at 5 A
                                                      Device 111  = 7.5 VA at 5 A
                                                     Then the total burden at 5 A will be
                                                     = 0.3 x  (5/1)'  + 5 + 7.5
                                                     = 7.5 + 5 + 7.5
                                                     = 20 VA
            (d) LT epoxy resin cast   (e) LT tape wound
                                                     Therefore,  one should select a 20 VA  CT.
       Figure  15.16  Typical  indoor-type  wound  primary  CTs  for   Similarly, if this value was required at the 1 A secondary, then
       measuring or protection (Courtesy: Kappa Electricals)   the total burden would be
                                                     = 0.3 + 5 x (1/5)'+  7.5  (1/5)'
                                                     = 0.3 + 0.2 + 0.3
       Protective devices  In view of the large variety of these   = 0.8 VA
       devices  such as static or electromagnetic, they may be   In this case one can select a 2.5 or 5 VA  CT.
       obtained from catalogues or their manufacturers.
                                                     2  The current element of a relay is wound for a wide
       Copperflexible leads (wires) The approximate resistances   range of current settings in terms of the rated secondary
       of such conductors at 20°C are provided in Table 13.15.   current of the CT, such as 1040% for a ground fault
       They can be estimated at the operating temperature (9OoC,   protection, 50-200% for an overcurrent and 300400%
       as in Table 14.5 or as desired).                 for a short-circuit protection. At lower current settings,
      VA burden = 12R                                   while  the  VA  requirement  for  the  operation  of  the
                                                        relay will remain the same, the VA capacity of the CT
      e.g.  the VA  burden  of  a  CT having  a rated  secondary   will decrease in a square proportion of the current. A
      current of 5 A with the length of the 2.5 mm2 connecting   CT  of  a  correspondingly higher  VA  level  would
       leads as  10 m.                                  therefore be necessary to obtain the reduced VA level,
   494   495   496   497   498   499   500   501   502   503   504