Page 495 - Industrial Power Engineering and Applications Handbook
P. 495

Instrument and control transformers: application and selection 15/469
         Corrrrol c.irc.ciit currmf                    Control circuit current
         IL = 43311 IO   = 3.94A
         and lead burden  = IL’ . K                    I, = 1268/110 = 11.53A
         where R is the resistance of the connecting wires at the   and lead burden  = 1 I .53’  x 2.035
         operating temperature  (90°C, as in Table  14.5)
                          76                                       = 270.53 W
                               +
                 = 6 X 35 X - 3.93 x  IO-’  (90-20)1   (2  ~
                             [I
                         I000                          :.  Total maximum inrush burden
                   (for details refer to Table  14.4)   I
                                                  ~            W = 555.7 + 270.53
                 = 2.035 R                        I
         :.Lead  burden  = 3.94’  x 2.035         i              = 826.23
                   = 31.59 W                           and VAr   = l14n.1 I
         :.  Total  maximum  steady-state  hold-on burden   l  1
           I+’= 197.85 + 31.59 = 229.44                :.  Maximum short-time VA  = d826.23’  + 1140.1 I’
                  And  VAr  = 384.9                                       = 1408.0
         :.Maximum  VA   = 4229.44’  + 384.9’     ~ I   at an inrush (short-time) cos 6 = 826.23
                        = 448. 1                                              1408.0
                          229.44
         at  a steadq-\tate cos  d = -                                      = 0.587
                          448. I0
                        = 0.51



        Rating of  control transformer
         Select a continuous rating = 500 VA
         at a  COS 4 = 0.51
         and short-time rating = 1500 VA
         at a coyb = 0.5X7
        The actual values a5 worked out above must fall below
        the  inrush curve of  the  selected control  transformer  of
        500 VA, as illustrated in Figure  15.12.

         15.4.3 Summary of specifications of a VT
         In Table 15.7 we list the data that a user must provide to
        a manufacturer to design a VT for a particular application.
        Some of the data chosen are arbitrary to define the speci-
        fications.                                                     cos @(of control circuit) -

         15.5  Precautions to be observed                                        0 587           0
              while installing a voltage               Figure  15.12  Checking  the  suitability of  the  500  VA  control
              transformer                              transformer for the required duty for Example 15 1

         I  Since a  VT forms an  inductive circuit,  it  generates
           heavy switching current surges which should be taken
           into  account  when  deciding  on  protective  fubeb. A   may cause local discharge and heating up of the inter-
           fuse with an appropriately high rating should be chosen   turns, leading to dangerous fault currents and ionization
           to avoid a blow-up during switching.          of oil in an oil-filled VT. It is advisable to provide a
        2  As a result of the generally high rating of protective   Bucholtz relay to protect oil-filled  VTs by  detecting
           fuses they provide no adequate protection against an   the presence of  gas in the cvcnt of a fault.
           inter-turn fault. For critical installations, and for HT   4  For  lower voltages (c 33 kV), any  fault on  the VT
           VTs particularly, a separate protection may be provided   will be detected by the protective devices installed in
           for inter-turn  faults.                       the main circuit.
        3  When an  HT-VT develops an  inter-turn  fault on the   5  Temperature  detectors  may  also be  provided  in  the
           HV  side, there  is no appreciable rise in the primary   windings  of  large VTs  as  are  provided  in  a  motor
           circuit current and which may not be detected. But, it   (Section  12.8).
   490   491   492   493   494   495   496   497   498   499   500