     Instrument and control transformers: application and selection  15/471
                                         (a) LT epoxy resin cast
      (b) LT fibreglass taped   (c) taped LT PVC            (d) Ground leakage relay  with CBCT
                     Figure 15.13  Ring type CTs for measuring or protection (Courtesy: Prayog Electricals)
       provide  greater  mechanical  strength  and  a  better   (i) Rated secondary current
       insulation  system. They are more suitable for humid,
       contaminated and corrosive atmospheres  and for  all   This will be 1,2 or 5 A, 1 and 5 A being more common.
        HT  systems.  They  are mechanically  strong  and  can   All  measuring  and  protection  devices  are  also
       bear shocks and impacts.                      manufactured for these ratings only as standard practice.
                                                     A  1 A secondary  is not recommended  in higher  ratios
                                                     due to increased induced voltage on the secondary side
      Note                                           during an accidental open circuit on load. It may damage
      All HT CTs are normally  manufactured  with epoxy resin cast.
                                                     the  inter-turn  insulation  or  cause  a  flashover,  besides
                                                    being dangerous to nearby components or a human body,
       Fibreglass  tape (Figure 15.13(b)).  To make it more   if in contact. This we have illustrated in Example 15.8,
        compact.                                     under section  15.9.
        Polypropylene
                                                     (ii) Rated output
      15.6.1  General specifications and design
            considerations for current transformers   The standardVAvalues may be one of2.5,5,7.5, 10, 15
                                                     and 30 generally, depending upon the application, although
      The  rated  frequency,  insulation  systems  and  the   a value beyond 30 VA  is also acceptable.
      requirement of creepage distances will generally remain
      the same as for a voltage transformer  (Section  15.4.1).   (iii) Rated burden
      For  the  remaining  parameters,  the  following  may  be
      noted.                                         This  is  the  value  of  the  impedance  of  the  secondary