Page 493 - Industrial Power Engineering and Applications Handbook
        P. 493
     Instrument and control transformers:  application and selection  15/467
           maximum switching inrush VA burden of the various   consuming power. It is advisable to add the VA burdens
           auxiliary devices connected in the  switching circuit   vectorially  rather  than  algebraically.  Since  a  control
           such as contactors, timers and indicating lights. Unless   transformer  may  feed  more  auxiliary  components and
           specified, the short-time VA burden of the transformer   devices consuming  power  compared  to  an  instrument
           will be a minimum of eight times its rating at 0.5 p.f.   VT, the VA rating of such transformers is generally higher
           lagging.  It  can  be  expressed in terms  of  VA  versus   than of an instrument, metering or protection VT.
           cos 4 and drawn in the form of  an inrush curve, for   Algebraic  summation  will  lead  to  a  higher  VA
           easy selection of a transformer rating (Figure 15. IO).   requirement than necessary. The transformer should not
         5  Voltage regulation  In view of heavy currents during   be too small or too large to achieve better regulation in
           the  switching  of  an  auxiliary  circuit,  the  reactance   addition to cost. From Figure  15.11 the  following may
           and the resistance drops of these transformers should   be derived:
           be  designed  to  be  low  to  ensure  a  high  degree  of
           regulation  during  a switching operation. Regulation   VAr=W+VAr
           of  up  to  6% for  control  transformers  rated  for  1.0
           kVA and above and up to  10% for smaller ratings is   or   VAT = ,/W2 + VAr’
           considered  ideal  (NEMA  Standard  suggests  these
           values as 5%).
             For  brevity,  only  the  more  relevant  aspects  are
           discussed here. For more details, refer to IEC 60044-   where  VAT = Total  VA burden
           2 and IEC 601 86, for instrument voltage transformers   VA = VA burden of individual component
                                                                     +
           and IEC 60076-3 for control transformers.          w= w, w, + ...
                                                       and   VAr = VAr, + VAr2 +. , .
         Application                                   W,, W,,  VAr, and  VAr,  are  the  active  and  reactive
                                                       components respectively of the VA burden of a device at
         These may be used to feed the solenoid or the motor of   a p.f. 4,  and &.
         an interrupting device (such as an electrically operated   The following may be ascertained when selecting the
         breaker), indicating lights and circuits, auxiliary contactors   rating of a control transformer:
         or relays, electrical or electronic timers, hooters or buzzers,
         and all such auxiliary components and devices mounted
         on a  controlgear  or a  switchgear  assembly requiring  a   Maximum  hold-on  (continuous)  VA burden  and  the
         specified control voltage.                      corresponding  p.f.  of  all  the  devices  likely  to be  in
                                                         service at a time.
                                                         Pick-up VA or short-time VA: An electromagnetic device
         Procedure to determine the  VA rating of        such as  a  contactor  or a  timer  carries  a  high  inrush
         a control circuit                               current,  also  known  as  ‘sealed  amperes’,  during  a
         The total VA level of a control or an auxiliary circuit is   switching  operation  and  it  is associated  with  a high
         the  phasor  sum  of  the  VA  burdens  of  each  individual   momentary pick-up  VA burden on the circuit and the
         component  and  device  connected  in  the  circuit,  and   feeding control transformer. The effect of the maximum
                                                         momentary pick-up VA burden and the corresponding
                                                         inflow p.f. of all the components likely to bc switched
                                                         at a time must be calculated.
                                                         Maximum lead burden of the connecting wires under
                                                         the above conditions.
                                                         The control  transformer  to  be  selected  may  have  a
                                                       rating  nearest  to  the  maximum  hold-on  VA burden  so
                                                       calculated and must be suitable to feed the required inrush
                                                       current  at  the  p.f.  so  calculated  without  affecting  its
                                                       regulation.  So long  as these  two points fall below  the
                                                       inrush  curve  of  the  control  transformer,  its  regulation
                        Cos I$  (of control circuit) -
               0  01  02  03  04  05  06  07  08  09  10
          Figure 15.10  Inrush characteristics  of  a control transformer   Figure 15.11  Phasor representation of a Load (VA burden).





