Captive (emergency) power generation 16/513

                 Generator (G)
                 214  : Impedance protection or distance back-up protection
                 324  : Anti-motoring protection or low forward power protection
                 404  : Loss of excitation or loss of field protection
                 464  : Negative sequence protection
                 49-43   : ‘RTD’ protection
                 59-43   : Over voRage/Hz protection
                 64-G &  : Generator stator ground
                 51-G   fault protection
                 64-GF  : Field ground protection
                 78-G   : Pole slipping protection or out of step protection
                 814  : Abnormal frequency operation
                 87-G   : Differential protection
                 Generator Transformer (GT)
                 49-GT  : ‘RTD protection
                 51N-GT:  Ground fault protection
                 63-GT  : Gas protection
                 64R-GT:  Restricted ground fault protection
                 87-GT  : Differential protection







                            Main bus



                -
                I








                                                                        Unit auxiliary transformer (UT)
                                                                        49-UT   : ‘RTD’ protection
                                                                        51-UT   : Over-current protection
                                                                        SIN-UT  : Ground fault protection
                                                                        63-UT   : Gas protection
                                                                        87-UT   : Differential protection
                                                                        64R-UT  : Restricted ground fault
                                                                               protection
















                  Protection of unit auxiliary transformers no. 1 and 2 (shown only one transformer)


        Figure 16.14  A typical protection scheme  in a  large generating station