Page 540 - Industrial Power Engineering and Applications Handbook
        P. 540
     16/514  Industrial Power Engineering and Applications Handbook
        (f) Overvolts per Hertz protection (V/Hz) (Relay Code   or transient instability or due to loss of excitation or
           59-G)  Per unit voltage divided by per unit frequency,   out-of-phase  synchronism.  Out-of-step  (phase)
           called V/Hz,  is proportional to flux in generator and   operation  can  result  in  high  peaks  of  current  and
           generator-transformer  cores.  (See also Section  1.2,   frequency, and cause winding stresses, pulsating torque
           equation (1.5) and Section 6.2.2). Excessive flux can   and mechanical resonance. All  these may endanger
           cause serious overheating of metallic parts and melting   the generator windings. Loss of excitation relay may
           of generator core laminations. (See also Section 1.6.2.   provide detection of such a situation, but it may not
           (Aiv) eauations  (1.12) and (1.13).) Excessive flux   be reliable under all conditions. An MHO-type relay
                        ~,
                                 ~
                                     I,
           (V/Hz) ;an  be caused by  voltage regulator  failure,   is generally used to protect the generator from such
           load rejection or excessive excitation. Even though   a situation.
           V/Hz is more likely to occur when generator is off-   0) Abnormal frequency operation (Relay Code 81-
           line, it can also happen  when generator is on-line.   G)  For a generator connected to a power system,
             Normally  a two-stage protection  is provided  for   abnormal frequency operation may be the result of a
           V/Hz  protection.  If  V/Hz  exceeds  1.18 per  unit,  a   severe system disturbance. An isolated unit, however,
           protection  relay  trips  the  generator  within  two   can  operate at a  low  or high  frequency, due to  an
           seconds (typical). For V/Hz  1.1  to  1.18 per  unit, a   incorrect speed control adjustment or a malfunctioning
           protection relay trips the generator within 45 seconds   of the speed control device.
           (typical).                                      The generator can tolerate underfrequency operation
           Generator stator ground fault protection (Relay   for  long  periods,  provided  that  the  loads  and  the
           Codes 64-G and 51-GN)  The neutral of the generator   voltage are proportionately reduced. It can also tolerate
           stator normally operates at a potential, close to ground,   overfrequency operation, when the voltage is within
           through a high-impedance single-phase distribution-   the permissible limits.
           type transformer the secondary of which is shunted   If a system disturbance requires extra generating
           through a resistor that has a voltage relay device 64-   capacity, the generator may drop speed, reducing the
           G  connected  across the  resistor.  In  the  event  of  a   frequency proportionately. The under-frequency relay
           ground fault, current flows through the resistor and   81-G  will  detect  such  a  condition  and  operate  a
           the relay 64-G operates due to a voltage drop across   systematic load shedding in a programmed manner
           the resistor. An overcurrent relay, 5 1-GN, connected   in order to meet the load demand. If  the abnormal
           to the current transformer in the secondary winding   condition persists, the generator is taken off the main
           of the grounding transformer is used as back-up for   supply system.
           64-G relay.                                 (k) Differential protection (Relay Code 87-G)  Diffe-
           Exciter protection  Protective devices are incorpo-   rential protection to detect stator phase-to-phase fault.
           rated,  as  required  for  protection  of  the  specific   (I)  Surge protection  This is similar to that for motors
           excitation  system components and are  supplied by   (Sections  17.10 and 18.8).
           generator manufacturers  as  an integral  part  of  the
           excitation equipment. Some of the protective devices   Protection  of  unit auxiliary transformer (UT)
           are                                         49-UT     RTD  protection  for  warning  of  winding
             Field  ground  protection  (Relay  Code  64-GF)      overheating  (see  also  Sections  12.7 and
             The generator field winding is electrically isolated   12.8 ).
             from  ground. Therefore  one ground  fault  in  the   5 1 -UT   Overcurrent protection
             rotor windings will usually not damage the rotor.   5 1 N-UT   Ground fault protection
             However, two or more ground faults in the rotor   63-UT   Gas protection through a Bucholz relay
             windings will  cause magnetic and thermal imba-   64R-UT   Restricted ground fault protection
             lances, which may result in localized heating and   87-UT   Differential protection  to detect  a phase-
             may damage the rotor. Protection provided in the     to-phase fault.
             excitation system is used to trip the generator in
             the event of  a ground fault in the rotor windings.   Prntertion  of generator transformer (GT)
             Field overheating protection   This is a part of   49-GT   RTD  protection  for  warning  of  winding
             excitation system to prevent the field from prolon-   overheating.
             ged overcurrent  through  an alarm  or a signal. It   Overcurrent
             will  trip  the  generator  only  if  it  is  absolutely   protection   For overcurrent protection, comments are
             essential. The field winding can carry momentary     the same as for generator protection, 49-G
             overcurrents for a short period, expressed in terms   item  ‘e’
             of field voltages, as noted below:        5 1 N-GT   Ground fault protection
                                                       63-GT      Gas protection through a Bucholz relay
             Time (seconds)   10   30    60    120     64R-GT     Restricted ground fault protection
             Field voltage   208%   146%   125%   112%   87-GT    Differential protection  to detect a phase-
                                                                  to-phase fault.
           Pole slipping or out of step protection (Relay code   Note
           78-G)  This is a protection against loss of synchro-   Relay Code numbers are according to ANSI designations. For details
           nism. It can occur as a result of steady-state, dynamic   refer to Appendix  2.
     	
