Page 628 - Industrial Power Engineering and Applications Handbook
P. 628

Surge arresters: application and selection  18/593
        operation, on the one hand, and a lower temperature rise   18.2.6  Transient voltages (Figure 18.4(a))
        of the element, on the other.
                                                       The operating point shifts to near point 4 and beyond on
                                                       the  curve.  It  may  conduct  a  current  of  2.5-20  kA  or
        18.2.2  Maximum continuous operating voltage   more, during a very  fast-rising voltage surge.
              (MCOV), V, (point 1 on the curve of
              Figure 18.4(a))
                                                       18.2.7  Protective level (Figures 18.4(a) and (h)
        This  IS the power frequency operating voltage that can   For TOVs this is determined by  its low current region
        be applied continuously  (2 2 hours) across the arrester   (d) of less than 1A and for prospective transient voltages
        terminals without a discharge. It continuously draws an
        extremely low leakage current, IZnO, capacitive in nature,   by  its  high  current  region  (e) of  2.5-20  kA  (8/20 ,us
        due to ground capacitance. The current 15 in the range of   current  surge). In  this region  the  arrester must  have  a
                                                       high capability for energy absorption.
        a  few  ,LA. Therefore  maximum  continuous  operating
        voltage                                         The  ZnO  protective  characteristic  curves  of  Figure
                                                       18.4(b) also suggest that these protective characteristics
                                                       remain unaffected by variations in operating temperatures
             VI,,
         V, = - (phase to neutral)                     except in very low current ranges is that and immaterial.
             L3
        18.2.3  Rated voltage, V, (point 2 on the curve of   18.3  Basic insulation level (BIL)
              Figure 18.4(a))
        This  is  the  voltage  for  which  the arrester  is  designed.   BIL is the basic insulation level of equipment. When the
        The arrester can withstand this voltage without a discharge   system  TOV  or  voltage  surges  exceed  this  level.  the
        for a minimum  10 s under continuously rated conditions   equipment  may  yield.  In  the  latest  international  and
        (when  the  arrester  has  reached  its  thermal  stability),   national standards it is defined as follows:
        indirectly indicating an in-built TOV capability of  10 s.
        Now  it also draws a current, capacitive in nature, in the   1  For systems  1  kV<  V,,  5 245 kV.
        range  of  a few  mA. The lower this  current, the  lower   (i)  Rated lightning impulse withstand level (LIWL)
        will  be  the  loss  and  the  heat  generated  during  an   (ii)  Rated  short time  power  frequency  dielectric
        overvoltage  and  hence  better  energy  absorption  capa-   strength.
        bili tj.                                          (iii)  Prospective steep-rising TRVs (FOWs) that may
          Below the knee-point, in the MCOV and TOV regions   be  caused  during  a  switching  operation,  as
        particularly,  the  V-I  characteristic  (Figure  18.4(b)) is   discussed in Section  17.7*.
        sharply  drooping with  the  temperature  rise,  causing  a   For motors, switchgears and bus  systems see Tables
        higher leakage current. It is a deterrent to otherwise good   11.6, 13.2, 14.1 and 32.1 (A) and for other equipment
        performance  for it means higher losses and heat under   Table  13.2. For more clarity refer to Section  17.1.
        normal  as well  as TOV conditions. Although  this very   2  For systems having  V,  > 300 kV to 765 kV:
        low level has been achieved, research and improve-ment   (i)  Rated lightning impulse withstand level (LIWL)
        in  the  formation  of  a  ZnO compound  is  a  continuous   (ii)  Rated switchingimpulsewithstand level (SIWL)
        process  by  leading  manufacturers.  It  aims to  optimize   (iii)  Prospective steep-rising TRVs (FOWs) that may
        the use of this material for a still better performance by   be caused during a switching operation as noted
        attempting to flatten the droop as far as possible.   above or during a fast bus reclosing (Section
                                                               17.4) particularly with the line trapped charge.
                                                              Refer to Table  13.3".
        18.2.4  Reference voltage (point 3 on the curve of
              Figure 18.4(a))
                                                       *There is no rated withstand levels specified in these standards for
        This  is  a voltage close to the knee-point  of  the chara-   such surges. This will depend upon the system parameters  as noted
        cteristic. It is a point where it commences its conduction   later and must be specified by the user to the equipment manufacturer.
        and draws a current, resistive in nature,  in the range of   Equipment  may  he designed for more than  one BIL values  as
        a few mA. Typical values are 0.4-10  mA.       noted in the various tables referred to above for motors, switchgears
          The  design  and  configuration  of  ZnO disks  is  such   and other equipment. The choice of BIL for equipment for a particular
        that  this  resistive  current  is  more  than  the  capacitive   application  will depend upon the extent of exposure the equipment
                                                       may be subject to in normal service and the security level required
        leakage current it draws in the MCOV region.   by  the  system and the surge protection. For more  details refer  to
                                                       Section  13.4.1(3).
        18.2.5 Temporary overvoltage (TOV)              It  is  advisable to  select  the  lower value  of  the  BIL  wherever
              (Figure 18.4(a))                         possible, to save on the cost of equipment, particularly  when surge
                                                       protection  is being provided.  Equipment, however, exposed more
                                                       to  such onslaughts may he selected  with  a higher  BIL. Examples
        The operating point  1  temporarily shifts to near point 3.   are those mounted some distance from the surge arrester and have
        Now also the current is also resistive and in the range of   a  higher  protective  distance  leading  to  more  reflections  and
        a few mA.                                      transference of  surges.
   623   624   625   626   627   628   629   630   631   632   633