Page 720 - Industrial Power Engineering and Applications Handbook
P. 720

21/680  Industrial Power Engineering and Applications  Handbook

         10000                                                      Effects of A C currents (50 Hz) on a person
         5000                                                       at least 50 kg in weight
         2000                                                       Zone-1 - Usually no reactlon
                                                                    Zone-2 - Usually no dangerous physiological
          1000                                                            effect
          500                                                       Zone-3 - Usually no danger of heart failure
                                                                          (ventricular fibrillation)
        1 :::                                                       Zone-4 - Probability of  heart failure up to
                                                                           50%
                                                                           than 50%
        3 50                                                        Zone-5 - Probability of  heart failure more
        s
           20
        E   10
        K
            5
            2
            1
             0 1  02   05  1   2  3  5   10  20 30  50  100  200   500 1000 2000  5000
                       Current passing through the human body in mA (rms) +
                               Figure 21.1  EffeCcts of current  leakage through a human body


                            -
                       -
                        -
                  -~-  - - - - - - - -    -     R      and  electrocution,  while  the  latter protects  the  circuit
                          -
                           -
                 I                -   7  I
                -  a        -            I  I   Y      from fire risk. Normally the 300 mA GLCB is used as
                  I                      I             the incomer and 30 mA as the outgoing for the individual
                -  4                     1      B      feeding circuits.
                  I                      I
                  I                      I
                                                       Refer to Figure 2 1.2 showing a single-phase circuit breaker
                                                       having a thermal overcurrent and a magnetic short-circuit
                                                       element, OCR. A core-balanced transformer is arranged
                                                       in the circuit as shown. When the system is healthy, the
                                                       current through the phase, I,,  and the neutral, I,,  will be
                                                       equal and the magnetic effect of the load current on the
                                                       primary windings, P, and P2, will be almost zero. In the
                                                       event of  a ground leakage, I(, this balance  is disturbed
                                                       and some of the leakage current will  also flow through
                                                       one of the primary windings of this core-balanced CT, as
                                                       shown in the circuit. This will  cause a magnetic flux in
                                                       the core, inducing a voltage in the secondary winding S.
                                                       In the circuit shown, it feeds a rectifier circuit provided
                                                       on the secondary side of the circuit. This unit facilitates
                                                       a direct current flow through the leakage trip coil, which
                                                       trips the breaker. These breakers are extremely fast opera-
                                                       ting on fault (operating time may be le2s than 5 ms), and
                                                       have a low let-through energy. Refer to I- - t characteristics
                                                       (Figure  21.1). The  ground  fault  current  will  also  be
                                                       comprised of a current through the appliance, I,  (Figure
         Z,  -Ground  fault loop impedance             21.2). But  since the basic  purpose of  this device is to
         IA - Leakage current through the appliance  But for simplicity the   protect  the  human  body  from  an  electric  shock  or
            whole current is considered through the body only   electrocution,  we have considered  the leakage  current,
          if  -Leakage  current through the human body   I(, through  the body  alone to be  safer. To  ensure total
         * -Test  button to  check periodically the operation of  the ELCB   safety, the device should be able to detect this leakage,
                                                       assuming  there  was  nu  ground  current  through  the
                                                       appliance.  When  the  device will  be  able  to do so, the
              Figure 21.2(a)  Schematic drawing of an ELCB   circuit in any case will be protected.
   715   716   717   718   719   720   721   722   723   724   725