Page 719 - Industrial Power Engineering and Applications Handbook
P. 719

Grounding theory and ground fault protection schemes 21/679
       21.1  Protection of a domestic or an           body can endure, without damage has a relationship with
             industrial single-phase system           the leakage current through  the body  and its duration,
                                                      i.e.


       21.1.1 Effects of current passing through a
             human body and the body’s tolerable                                             (21.1)
             limits
                                                      where
       An electric current, rather than voltage, through a human   sb = shock energy in watt-seconds  (Ws)
       body may cause shock and can damage vital organs of   Ib = r.m.s value of the leakage current through the body
       the body as follows:
                                                            in Amperes (A)
                                                        tb = duration of leakage current in seconds (s)
          It may cause muscular contraction, unconsciousness,
          fibrillation of  the heart,  respiratory  nerve blockage   The energy, S,,  for  a  50 kg  body  is regarded  safe  at
          and burning. These are all functions of body weight.   0.0135 Ws and for a 70 kg body at 0.0246 Ws
          The muscular contraction makes it difficult to release
          an energized object if held by the hand and can also   :.   I, (50 kg) = /?   - -   (21.2)
                                                                      0.0135  - 0.116
          make the breathing difficult. The heart, being the most             K
          vulnerable organ of a human body, is damaged most,
          mainly  by  ventricular fibrillation, which  may result             OE
                                                                            =
                                                                     -
          in an immediate arrest of the blood circulation (electro-   and  I, (70 kg) = /y -   (21.3)
         cution). In Table 21.1 we provide likely intensities of
         body currents when lasting for more than a heart beat
          (nearly 60-300  ms or 3-15  cycles for a 50 Hz system).   Figure 21.1 as in IEC 60479-1 illustrates the various
                                                      zones of ground leakage current versus duration of fault
          It is generally seen that a human body can sustain a   and its effect on a human body.
          much  higher  current  at  a  lightning  or  switching   To enable the body to sustain a high fault current it is
          frequency (5 kHz or above) due to the extremely short   essential that the fault interrupting device (relay or release)
          duration of  such surges (30 ps  or less).
                                                      is  quick  responding.  For  domestic  applications,  it  is
                                                      recommended to be less than a heart beat.
         The current can pass through the heart, when the current
       passes through hand to hand, or through one hand and a
       foot. Current flowing between one foot to the other may   Note
                                                      Prevention from ground leakage as such is important, as it causes
       not be considered  dangerous, but  may cause muscular   corrosion through electrolysis and may damage the insulation of
       contraction and pain. The subsequent body fall, if it occurs,   wires due to ageing.
       may, however, be fatal as now the current can also flow
       through  the  hand  involving  the  heart.  Ground  fault   21.1.2 Use of ground leakage circuit breakers
       protection  emphasizes keeping  the fault current below   (GL CBs) *
       the fibrillation threshold  and for a period of less than a
       heart  beat,  in  the  range  of  60-300  ms.  It  has  been   It is likely that smaller installations, such as a domestic
       established that the electric shock energy which a human   light  or power  distribution  network,  and  single-phase
                                                      industrial  or  light  loads  may  not  always  meet  the
                                                      requirements, as discussed  in Section 21.2, Table 21.2,
       Table 21.1  Likely intensities of body currents when   due to the circuit’s own high impedance (other than the
       lasting for more than a heart beat (=  60-300  ms)   impedance  of  the  ground  conductors).  It  is  therefore
                                                      possible that the fuses, if provided for the short-circuit
       Sr.   Body   At frequency   Intensity          protection of  the system, may be too large to detect a
       no.   current                                  ground  leakage.  The  ground  leakage  circuit  breakers
            (d)  (HZ)                                 (GLCBs) provide an effective solution to this problem
                                                      and are easily available and extensively used. They are
       1    100     50-60       Lethal                extremely  sensitive to very  feeble ground leakages, of
       2    100     3-  10 kHz   Tolerable (because of   the order of  10 mA or more, and trip the faulty circuit
                                extremely short duration)
       3    60-100   50-60      Fatal                 within a safe period on the smallest leakage current and
       4    16-60   50-60       Breathing may become   provide effective protection  to the human body. Figure
                                difficult due to muscular   21.2 illustrates the tripping  scheme for such a breaker
                                contraction           and the principle of operation is discussed below. Normally
       5    10-16   50-60       It is the let-go current and   two types of GLCBs are in use, i.e. 30 mA and 300 mA.
                                makes it hard to release an
                                energized object if held by
                                hand                  *More commonly known as earth leakage circuit breakers (ELCBs)
       6    5-9     50-60       No dangerous effects   or residual current circuit breakers (RCCBs). They operate on the
       7    14      50-60       Threshold of  sensation
                                                      principle of residual current.
   714   715   716   717   718   719   720   721   722   723   724