Page 723 - Industrial Power Engineering and Applications Handbook
P. 723

Grounding theory and ground fault protection schemes  211683
                           System or equipment
                             under protection
                                                                                 R

                                                                                 Y
                                                                                 B
                                                                    I
                        1          ,.q &+ 4 4 + 4





                         -G                -G          =G              -G
                                  (a)                 (b)             (4
                                      (a) Only for a ground fault (G/F) protection
                                      (b) For 3-0/C  and  l-G/F  protections
                                      (c) For 2-0/C  and l-G/F  protections
                       Figure 21.5(a)  Unrestricted G/F protection schemes for three-phase three-wire systems


                           System or equipment
                             under protection
                                                                                 R

                                                                                 Y
                                                                                 B
                                                                                 N






                                            =G        -G
                                  (a)                (b)              (C)
                                      (a) Only for a ground fault (G/F)  protection
                                      (b) For 3-0/C  and  1-G/F  protections
                                      (c) For Z-O/C  and  l-G/F  protections
                        Figure 21.5(b)  Unrestricted G/F protection schemes for three-phase four-wire systems


         (b) show different methods of CT connections for a ground   The preferred normal settings in a ground fault relay
         fault protection. The fault current in this case need not   are  10-40%  or  20-80%  of  the  rated  system  current,
         be hery high. It should rather be limited to a low value,   depending upon the application. For a balanced load, a
         to limit damage to the equipment. As a rule of thumb it   setting of, say, IO-20%  is sufficient. For a system having
         may be up to the rated current of the feeding transformer,   more single-phase light or power loads, a higher setting
         or the rating of  the incoming feeder, or twice the rating   would be necessary,  depending  upon  the  likely single-
         of the largest outgoing feeder, depending upon the circuit   phase loads. This is to avoid false tripping on a healthy
         to be protected.                              system, as all the out-of-balance current will flow through
           The most common practice,  however, is to limit the   the neutral only.
         ground fault current to only half the rated current of the   The theory of operation of such a protection scheme is
         system, or the circuit that is being protected. This is also   based on the principle that in a balanced circuit the phasor
         in line with the universal practice of having the neutral   sum of  currents  in  the three healthy  phases  is  zero, as
         of half the size that of the phases. The neutral is normally   illustrated  in  Figure 21.7,  and the  current  through  the
         grounded to form a complete circuit through the ground   grounded neutral is zero. In the event of a ground fault,
         conductor in the event of a ground fault. Refer to Figure   i.e. when one of the phases becomes grounded, this balance
         2 1.6. showing a typical distribution network illustrating   is upset and the out-of-balance current flows through the
         the grounding circuits.                       grounded neutral. A healthy three-phase circuit. however,
   718   719   720   721   722   723   724   725   726   727   728