Page 726 - Industrial Power Engineering and Applications Handbook
P. 726

21/686  Industrial Power Engineering and Applications Handbook








              -





                                                                                    are wired in series
         A  number of  cables connected                 A  number of cables connected   * The relay contacts
                                                                                    for indication, alarm
             to a common load                               to a common load          or trip circuit.
              (a) Separate CBCT for each cable.           (b) Separate protective circuit for  each cable
                               Figure 21.10  Methods to wire a protective  circuit through CBCTs



        Since on a fault the power factor is normally low, Ire and   21.5.3  Mounting of CBCTs
        In( may be considered almost in phase, when
                                                       The following is  the  correct procedure for  the  proper
         Ip  2-  n(zre  +In0                           mounting of these CTs:
        Since  V, and  In( are  interdependent  parameters  the
        optimum design is achieved when In( at Vr is of the same   1  It is necessary to pass all the  3, 3i or 4 cores of the
        magnitude as the relay operating current, i.e. In(  2-  Ire.   cable  through  the  core  of  the  CBCT to  detect  the
          For high current systems, using more than one cable   unbalance or the ground leakage in 3-core cables and
        in parallel, the number of CBCTs will also be the same   only  ground  leakage  in  33- and 4-core cables.  To
        as the number of cables, as illustrated in Figure 2 1.10, in   explain  this  see Figures 21.11(a)  and (b). A  3-core
        which case                                       cable will  detect  an unbalance in  the  three  phases,
                                                         whether  this is  the result  of  unequal  loading in the
        IP = n[/, + N  . In(]  for N  number of CTs      three phases or a ground fault. However,  33- or 4-
          All such CBCTs have to be identical in turns ratio and   core cables will detect only a ground leakage as the
        magnetizing characteristics to avoid circulating currents   amount of  unbalance, when it occurs, will be offset
                                                         by  the flow  of  this unbalanced  current through  the
        among  themselves.  To  order  a  CBCT the  following   return path of the neutral circuit. When using only 3-
        information will be essential:
                                                         core cables, the load must be almost balanced otherwise
          Minimum primary ground leakage current         it will  send wrong  signals or a higher setting of the
          Nominal CT ratio. This may be such that on the smallest   relay will become essential to account for the out-of-
          ground fault the current on the secondary is sufficient   balance currents due to the feeders’ unequal loading.
          to operate the relay. Normal I, = SO, 100 and 200 A. It   2  In armoured cables, armouring must be removed before
          is recommended to be such that V, 2- 0.1 x knee point   passing the cable through the CBCT to avoid an induced
          voltage of the CBCT                            e.m.f.  through  the  armour  and  the  corresponding
          Relay setting                                   magnetizing current which may affect the performance
          CT secondary current,  1A or SA                of the CT.
          Minimum  excitation  current  required  at  the  relay   3  As such CTs are required to detect small out-of-balance
          operating voltage                              currents,  the  connecting  leads  should  be  properly
          Knee point voltage                              terminated  and  must  be  short  to  contain  the  lead
          Number of cables in parallel                    resistance as far as possible.
          Limiting dimensions and internal diameter (ID) of the   4  For high-rating  feeders using  more than  one cable,
          CT. ID will depend upon the size of the cable.   there  must be one CBCT for each  cable. Not  more
                                                          than  one  cable  must  pass  through  such  CTs. The
         21.5.2  Insulation level                         secondary of all such parallel CTs may, however, be
                                                          connected in series, across the common relay (Figure
         Irrespective  of  the  system  voltage,  a  CBCT  may  be   2 1.1 O(a)).
         designed for an insulation level of only 660 V. The cable   All CBCTs being  used  in  parallel  and  intended for
         insulation  of  the HT conductor is sufficient to provide   the  same  feeder must  have  identical  magnetizing
         the required insulation  between  the conductor and the   characteristics and calibration in order to relay identical
         CBCT.                                            signals. Even then small variations in the output may
   721   722   723   724   725   726   727   728   729   730   731