Page 730 - Industrial Power Engineering and Applications Handbook
P. 730

21/690 Industrial Power Engineering and Applications  Handbook

           equipment or circuits, requiring individual protection.
           Figure 21 .I6 illustrates the operation of the relay when
           the fault occurs within the protected zone. The scheme
           will  prevent  isolation  of  the  equipment  for  faults
           occurring outside the restricted zone (Figure 21.17).                  'I
        2  A delta-connected or an ungrounded  star-connected
           winding should also be protected through a restricted
           ground  fault  scheme,  otherwise  it  will  remain
           unprotected.  There is  no  zero  sequence or residual
           current in  such a  winding  to detect  a ground fault.








                                              B
                                                       *  The residual currents are equal and opposite, hence nullify and
                                                         the relay stays inoperative.
                                              N
                                                       Figure 21.17  Scheme for restricted G/F protection for a
                                                       three-phase four-wire system. Fault occurring outside the
                                                       protected zone

                                                         The arrangement will be similar to that for directional
                                                          protection of a delta side of a transformer, as discussed
                                                          later, with the use of a grounding transformer (Figures
                                                          21.19 and 21.20).

         Under healthy condition the unbalance residual current of the 3 phase   21.6.3  Unrestricted ground fault protection
         CTs is nullified by the equal and opposite current in the neutral CT.
         There is thus no current through the relay.   The CT provided in  the ground circuit is now removed
                         ~        _         ~         _  and the same scheme becomes suitable for an unrestricted
                         /r  + /v + /b  = /u
                                                       G/F or a combined G/F and phase fault protections. It is
                                                       true for a three-phase three-wire or a three-phase four-
         Figure 21.15  Scheme for restricted G/F protection for a   wire  system. This  scheme may  also be  arranged  for a
         three-phase four-wire system. Healthy condition
                                                       combined O/C and G/F protections as illustrated in Figures
                                                       21.5(a) and 21.5(b).
                                                       Application
                                                       This is the most common scheme in normal use for any
                                                       power system with more than onc fceder, connected to a
                                                       common bus, such as for distribution and sub-distribution
                                                       power  networks,  having  a  number  of  load  points,
                                                       controlled through a main incoming feeder. In a switchgear
                                                       assembly,  for  instance,  common  protection  may  be
                                                       provided at the incoming for a ground fault or combined
                                                       O/C  and  G/F  protections  as  discussed  above. In  such
                                                       cases, a restricted G/F protection may not be appropriate
                                                       or  required,  as  the  protection  now  needed  is  system
                                                       protection, rather than individual equipment protection.
                                                       The incomer  must  operate whenever  a  fault  occurs at
                                                       any  point on the  system. Moreover, for an LT system,
                                                       where  it  may  not  be  desirable  or possible  to  provide
                                                       individual  protection  to each  feeder, such a  scheme is
                                                       adopted extensively.
         The residual currents are additive and the relay can be set low.
                                                       21.6.4  Directional ground fault protection
         Figure 21 .I6  Scheme for restricted G/F protection for a
         three-phase four-wire system. Fault occurring within the   In  the  previous  section  we  discussed  non-directional
         protected zone                                protection of an equipment or a system. But for systems
   725   726   727   728   729   730   731   732   733   734   735