Page 732 - Industrial Power Engineering and Applications Handbook
P. 732

21/692  Industrial Power Engineering and Applications Handbook
        illustrated in Figure 21.21, and grounded neutral utilised,                 DM Power
        to provide the required residual current polarization, to   CTs   m          transformer
        actuate the ground fault relay.
                                                                '1   s2
        Note
        The two currents, residual and polarizing, are capable of  operating
        the relay.
        21.6.5  Current setting of a ground fault relay

        1  Selection of CTs for ground fault protection particularly
           needs more careful consideration of the fault conditions
                                                         current 'L
           and impedance of  the ground circuit, in  addition  to   Residual1
           the location  of  the CTs. This  is due to a rather  low   ~
           setting of  the G/F relay,  1040% or 20-80%  of  the   coil  ,
           full load current or even lower, as in mines and other
           sensitive locations. Too low a setting may even trip a   Current
           healthy  system  due to  ground  capacitance  leakage   polarizing I  ~
           currents (more so in HT circuits) or unbalanced currents   coil   ~
           through  the  neutral  (more on  LT circuits). In  core-   -_----
                                                              Directional
           balanced CTs detecting small leakage currents, it is   ground fault
           possible that during a phase-to-phase  fault there may   relay
           be transient spill currents through its residual circuit,   Current  polarization  through  the  grounded  neutral  of  a  grounding
           which  may  operate  the  low-set  and  more  sensitive   transformer
           G/F relay, which may not be desirable. To overcome
           this,  the  time  setting  of  the  relay  may  be  suitably   Figure 21.21  Typical circuit illustrating current polarization
                                                       scheme to operate a directional GFR
                                  A /D Power
            CTs                    transformer
                                                         adjusted so that the overload relay will operate faster
                                                         than the G/F, or slightly higher setting for the relay
                                                         may  be  provided  or  time  delay  in  the  trip  circuit
                                                         introduced.
                                                       2  In  another  situation,  when  the  ground circuit  has  a
                                                         higher  impedance  than  designed  it  may  be  due to
                                                         poor soil conditions, dry soil beds, rocky areas, poor
              Residua                                    grounding stations or inadequate maintenance. In such
              current                                    conditions,  the ground circuit  may provide  a  lower
               coil                                      fault current than cnvisaged. Sometimes an overhead
                                                         conductor may snap due to strong winds and fall on
              Current                                    dry  metallic  roads,  hedges  and  shrubs  causing
             polarizing                                  extremely low leakage currents, creating a hazard to
               coil                                       life and property. This may cause an  arcing ground,
                                                          leading  to  fire  hazards.  For  all  such  locations  and
                   ground fault                           situations, very low current settings (of the order of
                      relay                               5% of I, or even lower) or leakage current detection
                                                          through core-balanccd CTs may be adopted.
          Current polarization through the grounded
          neutral of aA/D power transformer            3  For circuits protected by HRC fuses for short-circuit
                                                          conditions,  the G/F relay  must  be  a  back-up  to the
         Figure 21.20  Typical circuit illustrating current polarization   fuses, and trip first on a ground fault. In other words,
         scheme to operate a direction GFR                Pt (relay) < 12t fuses.
   727   728   729   730   731   732   733   734   735   736   737