Page 727 - Industrial Power Engineering and Applications Handbook
P. 727

y  the neutral  circuit




                                 3-g  load     3-g  four-wire load   I,,   - Unbalanced current due to load-A













                                                                  This CBCT will  detect the unbalance  as
                                                                  well as the ground leakage currents
                                                                  This CBCT will  detect only the
                                                                  ground leakage current
                                                                  I,,  - Unbalanced  current due to load-A
                                                                  Iub - Unbalanced  current due to  load-8
                                                                  Iga Ground fault current of  load-A
                                                                   -
                                                                  Igh Ground fault current of  load-B
                                                                   -







                                               (b) On a ground fault

                      Figure 21.11  Detecting the unbalance and the ground leakage currents through  a CBCT


           occur which could affect the  sensitivity of  a circuit   Note
           using  more  than  one CBCT.  If  such  a  reduction  in   In an HT system it is recommended that each circuit he protected
           sensitivity is considered detrimental to the protection   separately  for  a  ground leakage as far as possible.  This is  to
          of the system or the equipment, it is advisable to use   localize the effect of the fault and to trip only the feeder of the
           a separate relay  with each CBCT (Figure 21.10(b)).   faulty  circuit. A  common  protection  in  the  incoming  is  not
                                                         advisable, except  for  cost  considerations, which  also will  be
           For a common  indication, alarm  or trip, the relays'   nominal for such a protection  scheme compared to the cost of
           trip conlacls may be  wired in series.        the  main  equipment.  Otherwise a  ground  leakage  in  the
        5  When using only single-core cables, the same method   downstream  may  trip  the  whole  system.  which  may  not  be
           should be adopted, as discussed above. Groups may   desirable. It is also possible that at the downstream. the ground
          be made of 3,  3;  or 4 cores (R, Y, B or R, Y,  B and   leakage is very feeble due to high ground loop impedance and
           N) of single-core cables, and one CBCT used in circular   may  not  be  sufficient  to be  detected by  the  common ground
          or rectangular form, whichever  is more convenient,   leakage protection  probided  at the incoming. It is also possible
                                                         that the setting of the relay is not so low as to detect this. Thus
           for each group.                               to provide a ground leakage protection for each individual circuit
   722   723   724   725   726   727   728   729   730   731   732