Page 731 - Industrial Power Engineering and Applications Handbook
P. 731

Grounding theory and ground fault protection  schemes 211691








                                    @---
          I                                                                         -L-[   Primary
                                                                                          windings
                                                          Residual  gw’c                i
                                                                                   ,/E
                                                                  ~
                                                          voltage  A
                                                        polarizing  coil   ~





                                                                                star connected
                                                                                secondary
                                                       Figure 21.19  A typical  scheme for a directional  GIF
                                                       protection relay



                                                       GFR to isolate the faulty feeder quickly than to wait for
                                                       the trip by the non-directional relay. This is to avoid  a
                                                       trip of the non-directional relay  ‘a’ on system A.
                                                         A directional G/F relay basically is a power-measuring
                                                       device, and is  operated  by  the  residual  voltage  of  the
                                                       system in conjunction with the residual current detected
                                                       by the three CTs used for non-directional protection, as
         Note                                          shown in Figure 21.19. To provide directional protection,
        a, b  - are non-directional GFR’s              therefore, a residual VT is also essential, in  addition to
         a’, b’-  are directional GFR’s                the three residual CTs. The voltage phasor  is used  as a
         *  Reverse direction  current, Iga through relay  b  would trip breaker   reference  to  establish  the  relative  displacement  of  the
                      to
          B’ and reduce  Iga zero.                     fault current. In healthy conditions, i.e. when the current
                                                       flows  in  the  right  direction,  V, = 0, (refer  to  Section
          Figure 21.18  System using directional  ground fault  relays   15.4.3 for  details),  and  the  relay  remains  inoperative.
                                                       The relay operates  only  when  the  current flows  in  the
                                                       reverse direction.
        with more than one source of supply in parallel, such as
        a power grid, receiving power from more than one source   Note
        (Figure 13.21) or an industrial load, having two or more   This relay  may be used only under unrestricted  fault conditions,
        sources  of  supply, one of  them being  a  captive power   with three CTs as shown. If the scheme is used under a restricted
        source, it is possible that a fault on one may be fed by   fault condition, with  the  fourth  CT in the neutral.  the directional
        the other sources and may isolate even a healthy system,   relay will remain immune to any fault occurring outside the zone of
        thus  rendering  the  system  unstable.  Such  a  situation   the three CTs, as the fault current through the fourth CT will offset
                                                       the residual  current, detected by  the  three  CTY (Section 21.6.3).
        requires discrimination of a fault and can be prevented   rendering the whole scheme non-functional.
        by  the  application  of  directional  G/F  protection.  The
        primary function of a directional G/F protection is thus   Current polarization
        discrimination.
          In the above situation, even an overspeeding motor on   Voltage  polarization  depends  upon  the  location  of  the
        a fault elsewhere would feed back the supply source and   relay and the location of the fault. It is possible that the
        require such protection. The protective  scheme isolates   residual voltage, at a particular location in the system, is
        the faulty source from being fed by the healthy sources.   not sufficient to actuate the voltage coil of the directional
        Figure 21.18 illustrates a simple power circuit provided   G/F relay. In such an event, current polarization is used
        with  a  directional  G/F relay.  In the event of  a  fault  in   to supplement voltage polarization. Current polarization
        syqtem B, source B alone would isolate. Source A would   is possible, provided  that a  star point is created on the
        not feed the fault as relay b’  would trip the breaker B’   system, even through a  AID power transformer. if  such
        and eliminate Iga. The relays are necessarily set at lower   a  transformer  is  available  in  the  same  circuit,  Figure
        aettings and at lower tripping times than the non-directional   2 1.20. Else a grounding transformer may be provided as
   726   727   728   729   730   731   732   733   734   735   736