Page 728 - Industrial Power Engineering and Applications Handbook
P. 728

21/688  Industrial Power Engineering and Applications  Handbook
          will be worth while without any serious cost implications. Such   Unrestricted G/F protection
          a philosophy, however, will not hold good for a system which   Directional G/F protection and
          is protected only through its incoming feeder and all the outgoing   Differential G/F protection (high impedance differential
          feeders are merely  isolators.  In  this  case  the  ground  leakage   protection is discussed in Section 15.6.6(1)).
          protection  will have to be centralized for the entire system and
          provided  in the incoming feeder only.
                                                       21.6.1  Protection through a single CT
        21.6  Ground fault (G/F) protection            This is the simplest method to protect an equipment against
              schemes                                  a G/F (Figure 21.12). It can, however, be applied only at
                                                       the source, which is a generator or a transformer, provided
                                                       that the source has no other parallel grounding paths in
        A scheme for a ground fault protection will depend upon   the vicinity. This is to avoid sharing of the fault current
        the  type  of  system  and  its  grounding  conditions,  i.e.   and false or inadequate detection of the fault current by
        whether the  system is three-phase  three-wire  or three-   the relay. This scheme is therefore more functional at the
        phase  four-wire.  A  three-wire  system  will  require  an   main  generating source, such as at the generator or the
        artificial grounding while for a four-wire system the type   generator transformer, having a low impedance solidly
        of grounding must be known, Le. whether it is effectively   grounded neutral.
        (solidly) grounded or non-effectively  (impedance) groun-   For any other equipment or system, such as shown in
        ded.                                           Figure  21.13,  the  fault  current  may  be  shared  by  the
          Grounding protection will depend upon the measure-   various grounding stations in the vicinity and the relay
        ment of the residual quantities (Vo or 1,) that will appear   may not sense the real extent of the fault, even when the
        across the ground circuit in the event of a ground fault.   system is effectively grounded. Apart of the fault current,
        As discussed above, in a  balanced  three-phase system   may now flow through the other nearby grounding stations.
        the voltage and current phasors are 120" apart and add   Moreover,  for  a  fault  on  another  feeder  spill currents
        up to zero in the neutral circuit. In the event of an unequally   may also pass through such relays and trip them (unwanted)
        distributed  system  or  a  ground  fault,  this  balance  is   when the relays are highly sensitive or have a low setting.
        disturbed and the out-of-balance quantities appear across   Such a scheme will also not discriminate when required,
        the neutral or the ground circuit respectively. The current   and hence will have limitations in its application. Neverthe-
        through the ground circuit will flow only when there is   less, it is common practice to apply single CT protection
        a  ground fault,  the  fault  current completing its circuit   through  neutral  circuits  of  the  grounded  transformers
        through the ground path. The normal unbalanced current,   anywhere in  the  system,  generation,  transmission  or
        due to unevenly distributed single-phase loads or unequal   distribution. Multiple groundings may cause problems,
        loading on the three phases, will  flow only through the   but this is taken into account at the desigdplanning stage.
        neutral circuit.
          In a phase-to-phase fault, however, the system will be
        composed of  two balanced  systems,  one with positive
        sequence and the other with negative sequence compo-
        nents.  The  phasors  of  these  two  systems  individually
        will add up to zero, and once again, as in the above case,
        there will be no residual quantities through the neutral or
        the ground circuit, except for the transient and spillover
        quantities.
          The ground fault current may be detected through three   Neutral
        or four  CTs, one in  each  phase  and  the  fourth  in  the   solidly
        neutral  circuit  (Figures  21 S(a) and  (b)). Through  the   grounded \T
        neutral to discriminate the fault, as discussed later.   i
        Note                                            Figure 21.12  Ground fault protection through a single GT
        In  a  G/F the  three  CTs  will  also  measure  the  unbalanced  load
        current, if any, in addition to G/F current. For an appropriate setting
        of  the  relay, therefore, it  will  be essential that  the  likely  system         '
        unbalanced current be measured and the relay set in excess of this
        to  detect  a G/F. For  systems  feeding single-phase or unbalanced
        loads, prone  to  carrying  high  and  widely  fluctuating unbalanced
        neutral currents, it may be difficult to determine the likely amount
        of  unbalance and provide  a suitable setting for the  G/F relay. In
        such cases use of four CTs or core-balanced CTs (if it is a four-wire
        system) would be more appropriate.                I        I         I
          Below we discuss the more widely adopted practices
        to detect a ground fault, i.e.:
          Protection through a single CT               Figure 21.13  Limitation in using a single CTfor a G/F protection
          Restricted G/F protection                    when the equipment has more than one parallel ground path
   723   724   725   726   727   728   729   730   731   732   733