Page 729 - Industrial Power Engineering and Applications Handbook
P. 729

Grounding theory and ground fault  protection schemes  21/689
        21.6.2  Restricted ground fault protection
         When  it  becomes  essential  to  discriminate  between  a
         fault within the circuit to be protected from one outside
        the circuit. this scheme may be adopted. While doing so,
        it must be ensured that adequate ground fault protection
         is available to the remaining feeders, if connected on the
         same system.
                                                       of  residual
        For a three-phase three-wire system             induced
        (generally HT systetns)
        The  scheme  for  a  three-phase  three-wire  artificially   Impedance
                                                       grounded
        grounded system will require four CTs, identical in design   system
        parameters. turn ratio, error and magnetizing character-              7 oh      To trw
        istics.  Otherwise  spill  currents  may  occur  sometimes
        sufficient to operate inadvertently a low-setting or highly
        sensitive ground fault relay. The fourth CT through the   Note  All the four CTs must be wired with the same polarity
        ground circuit is used with the same polarity as the three   (a) Relay operates when the fault occurs within the protected zone
        CTs of the phases. Then only would the residual current
        of the phase CTs fall 180" apart from that of the ground          Equipment to   Direction of
        circuit CT. Such an arrangement will provide the desired          be protected   phase induced
        discrimination,  to detect the fault occurring  within the    /'               currents in the
        protected  zone. Figures  21,14(a) and (b) illustrate this
        discrimination  through  the  use  of  the  fourth  CT.  The
        residual current of the three-line CT, in a healthy condition,
        in the event of an unbalance in the system, is taken care
        of by  raising the setting of the relay to account for the
        unbalance.  as in  a core-balanced  CT. The fault current
        through  the  relay  will  flow  only  on  a  G/F occurring
        within the restricted zone as illustrated in Figure 21.14(a).
        For faults occurring outside the restricted zone, as shown
        in Figure 3 1.14(b), the fault current through the ground
        circuit CT will  be offset by  the  residual current of  the
        three-phase CTs and thus the relay will remain immune
        to such a fault.


        For a three-phase four-wire system
        (generally LT systems)                         Note  All  the four CTs must be wired with the same polarity
        A three-phase three-wire system is generally a balanced
        system  and  has  negligible  unbalanced  residual  current   *  Induced residual fault current through the phase CTs.
                                                         ~
                                                                _
                                                                      _
        through  the  three-phase  CTs. The  relay  for  a  ground   (ft  = ir + iy + Ib +   is equal and falls opposite to the
        fault protection can thus be set low. The scheme discussed   residual current is through the ground circuit CT.
        above is thus satisfactory for a G/F. But in three-phase   (7, + 7, + lb)  is considered zero under healthy condition.
        four-wire LT systems. which are generally unbalanced,   For small unbalances the relay is set a little higher.
        the above scheme poses a limitation as there may now be
        a substantial residual unbalanced current through the relay.   (b)  The relay stays immune to a fault occurring outside the
        For G/F protection. therefore, such a scheme will require   protected zone.
        a higher setting of the relay  to avoid a trip in a healthy   Figure 21 .I4  Scheme for a three-phase three-wire restricted
        condition. It  is  possible  that  this  setting  may  become   ground fault protection for an HT system
        sufficiently high. for highly unbalanced systems to detect
        an actual G/F and defeat the purpose of G/F protection.
        Such a situation can be averted by providing a fifth CT   Application
        in  the neutral circuit  as shown  in  Figure 21.15, which   1  A restricted ground fault is recommended for equip-
        obviously will have its excitation current direction opposite   ment that is grounded, irrespective of  its method of
        to the residual current of the three-phase CTs. Hence, it   grounding.  Unless  the  protection  is  restricted,  the
        will  offset the  bame,  and the relay can be set low.  It is   equipment may remain  unprotected. Generally, it is
        therefore  mandatory to use five CTs in LT systems for   an equipment protection scheme and is ideal for the
        adequate restricted G/F protection.              protection of a generator, transformer and all similar
   724   725   726   727   728   729   730   731   732   733   734