Page 721 - Industrial Power Engineering and Applications Handbook
P. 721

Grounding theory and ground fault protection schemes  21/681


























        1.  Core           (Courtesy: MDS switchgear  Ltd.)
        2.  Primaly winding
        3.  Relay                                     (Courtesy:  English Electric)
        4.  Ground fault indicator
        5. Test button tripping
        6.  Outgoing terminal
                         they can be interchanged
        7.  Incoming terminal
                          Figure 21.2(b)  Two-pole ground leakage circuit breakers (ELCBs or GLCBs)


       21.2  Ground fault on an LT system             current ratings for an LT system. At these values of currents,
                                                      the overcurrent releases will trip in about 130-370 seconds.
                                                      Refer to ‘Z2  - t’  characteristic curves of such releases as
       21.2.1  System protected through over current   shown in Figure 21.3. The HRC fuses will blow out in
             releases and HRC fuses                   about 40/60 seconds. Refer to ‘Z2  - t’ characteristic curves
       The value of ground loop impedance is always predeter-   of fuses, as shown in Figure 21.4.
       mined, depending upon the system requirement  and the
       type of  protection  available to the system, its accuracy   Table 21.2  Maximum impedances of ground loop, when protected
       to  detect  the  fault  and  time  to  operate.  For  systems   by overcurrent releases of circuit breakers or fuses
       protected through overcurrent releases or HRC fuses only,
       the  ground  loop  must  have  a  comparatively  low   Current rating of   Overcurrent of   Maximum desirable
                                                                                   impedance of ground
                                                                     the circuit breaker
       impedance.  It  will  allow  a  high  ground  fault  current   circuit fuse   MCCB or ACB   fault loop on a 240 V
       through the faulty circuit, sufficient to trip the over current-
       cum-short-circuit releases of the breaker if the circuit is   ‘a’   ‘b’     circuit (415/&)
       protected through  such releases  of  the breaker or blow                         240
                                                                                   z,  = ~  3a or 1.5b
       out  the  HRC  fuses, if  the  circuit is protected  through
       HRC  fuses.  Such a  requirement  is more  desirable  for                   R
       higher rating  systems, where discrimination  between  a   5   10           16
       healthy and a faulty condition by  such devices may be   10   20             8
       difficult. Medium-rating systems may cause a relatively   15   30            5.3
       much higher fault current and be automatically protected,   20   40          4
       as the normal ground fault current would be sufficient to   30   60          2.7
       trip the short-circuit releases or blow out the HRC fuses.   40   80         2
         The rule  of  thumb  to determine the  ground  loop   60    120            1.33
                                                       80
       impedance is to consider the ground fault current as one   100   160         1
                                                                                    0.8
                                                                     200
       and a half times that of the overcurrent setting of the circuit   125   250   0.64
       breaker for breaker-controlled  systems (a fault condition   150   300       0.53
       for a breaker) or three times the rating of the fuses, for   175   350       0.46
       fuse-protected systems (an overcurrent condition for the   200   400         0.4
       fuses). Based on this rule, Table 21.2 suggests the optimum   300   600      0.27
       values of ground loop impedances for circuits of different   400 etc.   800 etc.   0.2
   716   717   718   719   720   721   722   723   724   725   726