Page 739 - Industrial Power Engineering and Applications Handbook
P. 739

Grounding practices 221699

         The performance of  this type of electrode grounding is
         almost the same as for the pipe grounding (Section 22.1.2)
         as  is  the  variation  in  resistance to the ground with  the
         length  of thc clcctrodc as in Figure 22.4.

         Example 22.3
         The resistance to ground for a 100 mm x 5 mm, 5 m copper
         strip, buried  at a depth of  1.5 m, having a soil  resistivity of
         100 ilm
                          2x500'
         R=  100 x  100  X  log,  ___ -
            2 x ilx 500    150 x  10
          = 3 185 log,  33333-  1  = 3 185 x 581 - 1
          = 17 50 il
         If the length of the strip is 25 m. other parameters remaining
         the same, then
         R=  100 x  100   2 x (2500)'   -1
            2il~2500~'~~~
                           150x10
          = 0.637 log,  8333.33 - 1
          = 0.637 x  9.03 - 1
                                                                                        3
                                                                               2
                                                               0     Number of  electrodes (stations) -
                                                                                                 4
                                                                       1
          = 4.75  0
         22.1.4  Choice of grounding method            Figure 22.5  Likely variation  in  ground resistance with more than
                                                       one electrode  connected in  parallel
         1  The  normal  ground  impedance  in  LT  systems,  is
           generally high. To achieve a ground fault current of
           the order of 1   to 3 times the rated current, necessary
           to protect a low current system against a ground fault   Plate grounding
           a\ discussed in Section 2 1.2. I, would be dificult unless   For two electrodes - 50%
           adequate  measures  are  taken  with  the  grounding   For four electrodes - 256
           stations to have as low a ground impedance as possible.
           To  achieve  this.  the  grounding  stations  are  made   Pipe, rod or strip grounding
           elaborate.  at  adequate  depth,  with  proper  chemical
           treatment  and  watering  arrangements  to  ensure   For two electrodes  ~  60%
           sufficient moisture throughout the year. This is attained   For three electrodes - 45%
           by  a  perforated pipe  driven froin ground level  up to   For four electrodes - 35%
           the  electrode.  See Figures  22.1  and  22.3,  showing   For more accurate calculations refer to BS 7430. The
           typical  arrangements  of  a grounding  station, with  a   likely  variation  is illustrated in the form of the graph
           plate  grounding  and  a  pipe  grounding  respectively.   in  Figure 22.5.
           Despite this,  the  ground  resistance  may  still  be  too   The  resistance to ground  would  vary  with  depth of
           high  to meet  the design parameters.         the electrode. A minimum depth of 1.5 in from ground
             To  overcome  this,  a  number  of  such  grounding   to the top of  the electrode is considered  mandatory.
           stations (two being a minimum  to provide  a double   and even deeper to reach  damp soil.
           grounding system) may be essential and connected in   A  pipe  or strip  grounding  is more  effective than  a
           parallel  to achieve the required low value  of  ground   plate grounding.
           resistance. A cumulative resistance of up to 2.5 R is   The size of  the  plate, the  length  of  the  pipe  or the
           considered satisfactory. However, for more effective-   strip may be altered to obtain a lowei- balue of ground
           ness and to make  the ground protective circuit more   resistance.
           sensitive. a resistance of  up to  1  R would  be better.   The choice of the metal (Section 22.4) for the grounding
           The  grounding  stations may  be  separated, centre to   electrode  will  depend  upon  the  corrosion  factor of
           centre.  by  2  in  or  more,  to  be  out  of  each  other's   the soil. But all metals are equally good and possess
           resistance Lone. A better gap would be around 4.5 to   a life span of 12 years and more. For a longer working
           6 m, when full ground resistance may be achieved by   life, the thickness of the electrode may be  increased
           each  electrode  without  infringing  on  the  resistance   as  discussed  in  Section  22.4.1.  GI*  being  a  more
           rime of the other electrodes as well  as economizing
           on the  number of  electrodes. This use of  more than   -
           one grounding station in parallel  so that each station
           is out  of  the  resistance  zone  of  the  other  stations,   *Apparently GI seems to be the best metal as B groundiiig electrode.
                                                       But if  part of the zinc coating of the metal  is chipped due to poor
           would  alter their  cumulative resistance, generally as   coating or to any other reason. the metal is rendered prone io rapid
           follows according to Hund Book ofElectrica1 histullu-   corrosion  and  erosion  and  may  fail  with  passage  of  time.  Some
           lion  Pructic.e.s by  E. A. Reeves:         users  therefore  prefer  lo use hare  MS conductor rather than GI.
   734   735   736   737   738   739   740   741   742   743   744