Page 744 - Industrial Power Engineering and Applications Handbook
P. 744

22/704 Industrial Power Engineering and Applications Handbook
        22.5  Jointing of grounding                    22.8  Tolerable potential difference at
              conductors                                     a location

        As discussed in Section 29.2.5, jointing of two different   We discussed in Section 2 1.1.1  the maximum tolerable
        metals (copper being one) causes electrolysis at the joints,   currents through a human body and their duration. The
        leading  to  corrosion and failure of  the joint. To  avoid   potential difference in a ground conductor at any point
        this, it is recommended that the same procedure be adopted   where a human body may come into contact with it during
        as discussed  in Section 29.2,  and where the electrode   the  course  of  a  ground  fault  should  be  such  that  the
        and the connecting ground strip are of the same metal,   resultant  current  through  the  human  body  will  remain
        that the joints are riveted or welded with the same metal   within these tolerable limits.
        after making the surface. Soldering is not recommended.
                                                       22.9  Voltage gradients
        22.6  Maintenance of grounding
              stations                                 The likely positions, in which a human body may come
                                                       into contact with a phase or a ground conductor, and the
        To ensure that a grounding station has not deteriorated   corresponding  potential  differences,  that  he  may  be
        and its ground resistance  has not increased due to soil   exposed to, are illustrated in Figure 22.9.
        depletion  it  is  mandatory  to  carry  out  a  few  checks
        periodically to ascertain the resistance of the grounding   22.9.1  Tolerable step voltage, E,
        station. If  the ground resistance  is  found more  than  it
        was designed for, it is possible that by proper moistening   This is the difference in the surface potential to which a
        of the soil or by adding more salts or chemicals to the   human body may be subject when bridging a distance of
        grounding pit, the desired level of  ground resistance is   1 metre on the conducting ground through the feet without
        achieved once  more.  If  not, then  additional  grounding   being  in  contact  with  any  other  conducting  grounded
        stations may have to be installed to obtain the original   surface (position  1, Figure 22.9).
        level of the ground resistance.                 The safe step voltage, E,, should not be more than the
                                                       total resistance to ground through the body, R2f,b (Section
                                                       22.10.1) x safe body current, Ib, as a function of time,
                                                       where
                       SECTION II
                                                       R,fsb = 6 . c, . ps + 1000 R (from equation (22.10),
                                                                              discussed later)
        22.7  Grounding practices in a power
              generating station                       and  I,  = - l6 for a SO kg body, as in equation (21.2)
                                                                 fi
        This is a vast  subject, on which extensive research has   -- 0.157  for a70 kg body, as in equation (21.3)
        been done by many authors over the years. The grounding   -   Jt
        stations in such areas are normally spread over the entire
        station,  and  sometimes  may  even  extend beyond  its
                                                               (6
        boundary to achieve the desired results. Here we discuss   .*. Es(5") I C,  ' ps + 1000) x   ~ O.  lii   for a 50 kg body
                                                                 '
        briefly, the basic  criteria  behind  the  requirement  of  a
        grounding  system  in  a  power  station  and  its  design                           (22.5)
        considerations.
          The magnitude of ground voltage in such areas in the   and   (6 . C, . pE + 1000) x  ~ 0'1s7 for a 70 kg body
        event of  a ground fault is very high, due to high  system               lir
        voltage. On a  ground  fault, the ground path resistance                             (22.6)
        may become a source of a high potential gradient across
        the grounding conductors at a particular location. It may   22.9.2  Tolerable touch voltage (E,)
        become high enough to prove fatal to a human operator   This  is  the  potential  difference  between  the  ground
        coming  into  contact  with  it.  To  limit  this  potential   potential rise (GPR) and the surface potential at a point
        difference  at all locations  within  a  tolerable  value and
        achieve an equipotential distribution of a ground conductor   where the person  is standing on the conducting ground
                                                       with  one hand  in  contact with  a  conducting  grounded
        over the station is the basic criterion on which is based   surface (position 2, Figure 22.9). The safe touch voltage,
        the design of a grounding system for a power generating   Et, should not be more than the total resistance to ground
        station.  Our  discussion  is  also applicable  to  outdoor
        switchyards and large sub-stations. For detailed working,   through  the  body,  R21ps (Section  22.10.1)  x  safe body
                                                       current, Ib, as a function of time, where
        it is advisable to refer to IEEE-80.
          The following basic data are important for the design   RZfps = 1.5 C, . p\  + 1000 R  (from equation  (22.11)
        of such a grounding system.                    discussed later)
   739   740   741   742   743   744   745   746   747   748   749