Page 743 - Industrial Power Engineering and Applications Handbook
P. 743

Grounding practices  221703
         Table 22.4  Size of  aluminium ground conductor for different   200 A. To calculate the main ground conductor size, assume
         sizes of  power cables for a grounding system   that the system is protected through HRC fuses. Then, based
                                                       on the previous assumptions,
                                                       Ground fault current,  I,  = 3 x 400
         1     up to 25  mm’   Same as the cable size                    = 1200 A
         7     Above 25-50  mm’   25 mm2
         3     Above SO  mm2   Approximately half the size of the   and  interrupting  time  of  400  A  HRC fuses,  referring  to
                               main  cable  size.  Say.  for  a  400   characteristic curves of  Figure 21.4  = 60 seconds
                               mm2  main  cable,  a  ground   :.  Ground conductor size for an aluminium conductor
                               conductor  of  185  mm’,  will  be
                               adequate

                                                       i.e. 25 mm x 3 mm [ 1”  x $1
         conductor. For a GI ground conductor, this size may be
         roughly doubled.
           For  large  feeders  and  HT  systems the  ground  fault
         current would be controlled naturally through the ground   or any other cross-section of  an equivalent area
                                                         If the conductor is of  GI then,
         circuit impedance and a smaller ground conductor may
         suffice.                                       s=- l2O0  ,/60
                                                            80
         Note                                          or = 116 mm2
         In LT systems, where the neutral is grounded, the neutral as well as
         the ground conductor may have to carry unbalanced currents  up 10   or 25 mm x  5 mrn  (1”  x 4”)
         half  the  rating  of  the  line  currents due to  single-phase loads.  A
         ground  conductor  should  also he  rated  for  the  same  size as  the   or any other cross-section of  an equivalent area.
         neutral.  irrespective of the setting of  the relay.   It could similarly be calculated for the individual outgoing
                                                       circuits, or considered equivalent to half the cable size being
                                                       used to feed the circuit.
           Now  equation  (22.4) as  suggested  by  BS  7430 will
         apply, which is based on our discussions in Section 2 1.3.1,
         where the ground system is normally predetermined for   Example 22.5
         three times the rated current of  the circuit for an HRC   If a distribution system is fed from a 1600 kVA, 11 kV/415 V,
                                                       transformer, then
         fuse-protected system or one and a half times for an over
         current release-protected system:                 1600 x  1000 A
                                                        I, =
                                                               x 415
                                               (22.4)    = 2225 A
         where                                         If the system is protected through overcurrent releases, then
         S  = crosyectional area of  a bare ground conductor in   applying the same assumptions as before:
            mm- .                                      Ground fault current,  I,  = 1.5 x 2225 A
         !g  = r.m.s.  value of the ground fault current in amperes
         K  = r.m.s.  current density in A/mm2. This will  depend   and the  maximum tripping  time  at  this current,  referring to
            upon the material of the conductor and its maximum   characteristics curves of  Figure 21.3.
            permissible temperature. For more common metals   = 370 seconds
            it may have the following values, assuming the initial
            temperature of the conductor to be 4OOC.    :.  Ground conductor size for an aluminium conductor
            Copper     = 205 A/mm2, assuming the final     1.5 x 2225 %/m
                        temperature to be 395°C         S=   126
            Aluminium  = 126 A/mm’,  assuming the final
                        temperature to be 325°C          = 509.5 mm2
            Steel  or GI  = 80 A/mm’,  assuming the final   or  100 mm x  5 mm
                        temperature to be 500°C
          t = duration of  fault in  seconds (operating time of  the   or  100 mm x  6 mm
            protective device).                        or any other cross-section of an equivalent area.
                                                         If the conductor is of  GI then
         Note                                           s =  1.5 x 80 2225 ,,m
         For other grounding materials.  or hazardous locations requiring  a
         much lower end temperature. refer to BS 7430.
                                                         = 802.5 mm2
         Example 22.4                                  or 80 mm x  10 mm or
         Consider a power distribution system having the main incoming
         feeder rated for 400 A and the outgoing feeders rated up to   any other cross-section of  an equivalent area.
   738   739   740   741   742   743   744   745   746   747   748