Page 746 - Industrial Power Engineering and Applications Handbook
P. 746

22/706 Industrial Power Engineering and Applications Handbook

       the  grounded  grid  potential  may  be  regarded  as  zero,   and its duration. In an automatic reclosure power
       except transferred voltages and surge pilferages that may   system, reclosure  after a  ground fault is common
       be caused during a transient state (Section 18.5.2). During   practice in modern power systems. This may result
       a ground fault the current will flow through the grounding   in repeat  shocks in quick  succession  to  a  human
       grid and cause its potential to rise with respect to a remote   body coming into contact with the ground conductor.
       ground. This voltage rise is seen to go up to 25 kV, but   Although this situation may last for less than 0.5 s,
       generally  not  beyond  10 kV  (IEEE  367) and  can  be   it may prove fatal. A reasonable allowance for such
       expressed by                                       an eventuality should be made when  deciding on
                                                          the clearing time.
       GPR  0~ I,  . R,
       where Ig = fault current through the grounding grid   Since a switchyard is normally connected to more than
       and  R, = grid resistance at the station grounding grid,   one supply system, the ground fault current in a power
                with respect to the remote ground.    station is contributed by  the power plant  as well as by
                                                      the  switchyard and  the  transmission  networks.  The
       The larger the grounded grid area, the lower will be the   following possibilities may arise:
       grid resistance,  and the  lower  the  GPR  and the  mesh
        voltage.
                                                      1  When  there  is  a  fault  in  the  local  generating  area
                                                         (Figure 22.10(a)) the return path will be through the
        22.9.5  Transferred voltage (Etr)                grounded neutral of the generator. The switchyard's
        This may also be considered to be a type of touch voltage   other remote power  sources  may  also contribute to
        where the voltage may be transferred into a switchyard
        or a generating area as a result of a ground fault somewhere   Remote   Local
        in the power network in one of the supply sources and a   source      power station
        person standing in the local area of one grid station comes
                                                                    The step and touch
        into contact with a grounded conducting part, grounded  i.
        at a remote grid station or vice versa (position 4, Figure   voltages are not affected
        22.9). In  such a  situation, if  a ground fault occurs, the   in- the generator area   + 191
        potential to ground may exceed the full GPR of the local                        L
        grounding  grid  where  the  person  is  standing. The
        transferred voltage may exceed the sum of the two GPRs   GT            GT
        of the two grounding grids, due to the induced voltages
        in the steel structures, neutral wires and metallic pipes in   TG   L---+
        the  vicinity.  It  is  not  practical  to  make  provisions  for                     I  I
        grid. To  safeguard  a  human  body  from such  voltages,  +                     11   I  I
        such an eventuality in the design of a station grounding
        IEEE 80 has recom-mended providing isolating devices,   I    O/G                 11  I1  41  ,  I  I
                                                                                         11
        surge  arresters or  display  danger  boards  at  suitable   l---------------------------~Lf-   192
        locations. For more details, refer to this Standard.   'Ig2 will exist only if the source is grounded star
                                                       [If it is A  or isolated neutral /g2  = 01
        22.9.6  Design parameters                               (a) Fault at the local area
        There  are  a  few  important parameters  that  must  be   Remote               Local
        determined before beginning the detailed engineering of   source             power station
        a grounding station.
        Maximum ground grid current and its duration
        This is the maximum grid ground fault current, IG, that
        may occur during the lifetime of the power plant. It may
        increase to the sum of two GPRs as noted above, ;.e. up
        to  80 kA or even higher (IEEE 367). For  system fault
        levels refer to Table  13.10. It is advisable to carry  out
        fault current studies every few years to assess the actual
        fault level compared to those considered  at the time of
        designing the grounding system. It is possible that the
        generating capacity of the power station and so also its
        fault level has increased with time.                              OIG
                                                                         19 1
                                                       Y~L------------)-----------------'
         t, - duration of fault. Typical values may range between   192
            0.25 and 1.0 s                                        (b) Fault at a remote location
        tsl - shock duration. The value may be considered  by   Figure 22.10  Contribution to ground fault currrent by other supply
            keeping a safety margin in the allowable body current   sources when more than one system IS operating in parallel
   741   742   743   744   745   746   747   748   749   750   751