Page 751 - Industrial Power Engineering and Applications Handbook
P. 751

Grounding practices  22/71 1
          where                                          each generator and the GT at point 6, considering the lower
           1, = symmetrical r.m.7. value of the zero sequence fault   value of  the impedances to be on the safe side,
              current
           Vt = line voltage                             = (16 - 1.6) + (14 - 1.4)-  200
                                                                           250
          Z, = positive sequence equivalent system impedance,
               Q/phase at the location of  the fault     = 14.4 + 10.08
          Z7 = negative sequence equivalent system impedance,   = 24.48%
               Q/phase  at the location of the fault.
          Z,, = zero  sequence  equivalent  system  impedance, a/   Since  all  three  generators  are  operating  in parallel,  the
              phase at the location of the fault.        impedance of  each circuit,  as calculated  above,  will fall  in
                                                         parallel and the equivalent impedance will become
          It  is  also  possible  to  estimate this,  if  the  system  unit   _-   +-+-  1   1
                                                              1  --
          impedance is known, when the maximum fault current   Z,,   24.48   24.48   24.48
               Full load current of the system                    24.48
                                                                    3
             =  Unit impedance of the system             or   z,,  = -
             = - 100%                            (13.5)   or 8.16% (0.0816 P.u.)
                1
                  x
               Z,l                                       Full load current at base MVA
          Example 22.7
          Consider  a  switchyard  receiving  power  from  three  of  200
          MVA, 15.75 kV generating sources, having an impedance of   = 0.875 kA
          16 5  10% each and feeding the transmission  lines through   0.875
          15.75/132 kV, 250 MVA generator transformers (Figure 22.1 7)   :.   I  - -
          with an impedance of  14 f 10% each (Table  13.8).   ' - 0.0816
            Considering  the  system  fault  level  at  32.8 kA, calculate   = 10.72 kA
          the ground fault contribution by the generating units;
            In this case the sources feeding the fault are generators   Since  the  system  fault  level  is  32.8  kA,  the  ground  fault
          and not generator transformers (GTs). The GTs are only current   contribution by the other sources connected on the grid
          limiters and introduce their reactances into the circuit. Since
          the ratings of  the generators and the GTs are different, it is   = 32.8 - 10.72
          mandatory to first convert them to a common base, say, 200
          MVA in this case. Therefore the combined unit impedance of   or   22.08 kA



                                200 MVA            200 MVA              200 MVA
                          15.75kV
                                                                      -
                                                                       -
                                                                           I
                             250 MVA            250 MVA              250 MVA






                           1L                4
                                              I
                                        lO/G
                                                       -
                    Power plant     -              I   -            -
                                                                    i-l
                    ground bus               T  1   I  ____  __-_  - ___--  11  ,
                                                        ~
                               Fault fed by other   ~   10.72kA      I
                               sources connected                     I
                               on the grid         I  I             i
                                                                    -
                                                                    5
                                                                     I
                                                                     l
                                                          I ______- -1

                                         Figure 22.17  Illustration of  Example 22.7
   746   747   748   749   750   751   752   753   754   755   756