Page 756 - Industrial Power Engineering and Applications Handbook
P. 756

@e-                                           that the actual touch E,  (actual) and step voltage E,  (actual)
        22/71 6  Industrial Power Engineering and Applications Handbook
                                                         After  the final  designs  are complete  it  is  recommended

                                                       are  rechecked for  both power  plant  and  switchyard areas
                                                       separately, to ensure that they are within the tolerable limits
                                                       as determined above. After the ground stations  have been
                                                       finally  installed the actual step and touch voltages must be
                                                       measured to verify the designs.

                                                       Note
                                                       The above example illustrates a simple procedure to design
                                                       a  ground  mat  in  a  large  power  generating  station,  inter-
                                                       connected to external supply sources through a power grid.
                                                       The procedure would be the same with a large switchyard,
                                                       receiving and transmitting large powers.
                                                         For small power houses, which may be captive and small
                                                       switchyards or sub-stations, receiving and distributing currents
                                                       to industrial or domestic loads, such an elaborate design is
                                                       not required and simple grounding stations as discussed in
                                                       Section 22.1 will be sufficient.





        Figure 22.20  A  simplified  layout  of  Figure 22.19,  illustrating  the
        sharing of fault current by the station grounding grid and the switchyard
        grounding grid on fault
   751   752   753   754   755   756   757   758   759   760   761