Page 753 - Industrial Power Engineering and Applications Handbook
P. 753

Grounding practices 22/713
         Example 22.8
         To  determine the  minimum  size of  ground conductor, consider a station grid  made of  Z,  coated steel, having the following
         parameters:

         Parameters     AS in /€€€-80                            As in IS 3043
                        1 or 0.001  kA                           1 or 0.001 kA
                        (to calculate a generalized factor in  rnm2/A)   (to calculate a generalized factor in  rnm'1A)
                        1                                        1
                        0.0032                                   0.0045
                        20.1                                     13.8
                        3.931                                    3.8
                        41 9                                     450
                        40                                       40
                         __-  20                                 ~-      20
                         0.0032                                  0.0045
                        = 293 (Table 22.5)                       = 202
                         .  A=   ~        0 001                              0 001
                                            ~~
                                          ~
                                                                     3.8 x lo4-
                              1' i/3931 00032x20 1 ) loge  ( 233 < 40 ]   /[ 0 0045 x 13 8 1 loge  [  ?:2',=?:   1
                                                293 + 419
                                     xlo
                                   0 001                               0.001
                             -                                   -
                              ,O  0061 log,  2 14                  I 0.006 log,  2.69
                             -    0 001                          -    0.001
                                   -                                 ~~~~   ~
                              I 0 6061 x  0 76                     \ 0.006 x 0.99
                            = 0.0147 mm'IA                       = 0.01 23 rnm'1A
                        or   ~   =68A/mm2                        or   ~   =81 Nmrn'
                           0.0147                                   0.0123
                                                                 Say 80 Almm'
         For an  /g  of  30 kA,
         size of  ground   = 0.0147 x 30 000                     = 0.0123 x 30 000
         conductor      = 441* mrn'                              = 369* mrn'
         *If  a future expansion in  the generating capacity of  the station is  envisaged, the grounding grid  conductor size so estimated
         may be enhanced  by a suitable decrement factor, Df (Section 22.9.6)


         voltages that a human body can endure. In actual service   The touch voltage diminishes up to 1 m depth
         these voltages of the grounding station should not exceed   of  the  grid  and then  rises  rapidly.  The  ideal
         the  prescribed  tolerable  limits.  Thc  grounding  station   depth for economic considerations may be taken
         design as carried out above must therefore be counter-   as 0.5 m when the touch and step voltages are
         checked  for these  limits. If  it exceeds these  limits the   reasonably low.
         station  must  be  redesigned,  to  contain  the  actual  step   Ki = corrective factor, accounting  for the  increase
         and touch voltages within the prcscribcd Icvcls.      in current densities at the far ends of the grid
           IEEE-80 has suggested the following formulae in terms   system, the resistivity of the soil and the average
         of  ground current and total  length of buried conductors   current density per unit length. Zti/L. of buried
         to determine the actual step and touch voltages:      conductors.
                                                           I,  = maximum fault current contributed by the power
                                  p' K, . K, . IC              generating units.
         Max. step voltage E,(actual)  =      (22.17)
                                       L                    L = total  length  of  the  buried  conductors  of  the
         and mesh or maximum touch voltage E,,(actual)         grounding station (equation (22.13)).

                                              (22.18)   Estimating the step voltage E, (actual)
                                                       In this case
         where
             p  = resistivity  of- the soil
         K,.  K,,, = geometrical factors, depending upon the more
                 important  parameters  such  as  area  of  the
                 grounding grid, its depth and conductor spacing   and the  maximum  step voltage is  assumed to occur at
                 and less important factors, such as diameter of   a distance equal to grid depth h. where /z  is more than
                 the conductors and the thickness of the finishing   0.25 m and less than 2.5 m. Depths less than 0.25 m may
                 surface by  concrete or gravel.       be rare:
   748   749   750   751   752   753   754   755   756   757   758