Page 809 - Industrial Power Engineering and Applications Handbook
P. 809

Power capacitors: behaviour, switching and improvement of  power factor  23/765
         power  factor, reducing the kVA demand and the strains          From main PCC
         on the main supply and distribution network. Technically
         speaking,  it  has  no  advantages  for  in-plant  power
         distribution, nor does it help to reduce the kVA strain on            l/C breaker
         the feeding cables or the loading on the power distribution
         feeders.  But  for  simplicity  and  ease of  control for the            To PFCR
         entire plant  it  is used most often.

         23.15  Automatic  PF correction of a
                system

         As  discussed  above,  for  an  industrial  or  power  plant
         application or an installation with a number of inductive
         load  points  a  grvup  capacitor  control  is always  more
         effective.  simple and  economical. Such an installation
         generally has a frequent variation in its load demand due
         to some feeders coming on the bus and some falling out
         at different times. There may be variation in the individual
         feeder’s load demand, such as a tool room, where not all
         the  machines  will  be working at a time, or a pulp  mill
         and  paper mill, where  the  paper mill has a continuous
         load, the pulp mill an intermillent one. A water treatment
         plant or a pump house are similar installations where all
         or some of the loads would be in operation at a time. For
         such installations. the total  capacitive load demand at a   PFCR - Power factor correction relay
         required power factor level  is worked out and the total
         capacitor banks are installed at a convenient point  and   Figure 23.35  Single-line diagram for an industrial load
         suitably  grouped  (banked) for the  type  of loading  and
         system demand. Each bank is controlled through a power
         contactor and a common power Lactor correction relay to
         automatically  monitor  and control the  power  factor of
         the system to a predetermined level, preset in the relay,
         by witching a few capacitor banks ON or OFF, depending          From main PCC
         upon the load demand and the power factor irieasured by              i
         the  relay. The  relay  actuates  the  required  number  of
         capacitor feeders through their  contactors.
           Automatic  correction  is  always  recommended  to
         eliminate  manual  dependence  and  to  achieve  better
         accuracy. It also eliminates the risk  of  a leading power
         factor  by  a  human  error  that  may  cause  an  excessive
         voltage at the motor and the control gear terminals.
           The  following  example  illustrates  the  method  of
         selecting the capacitors’ value, their grouping and their
         control for a system having a number of load points.

         Example 23.8
         Consider a system shown in the single-line diagram of Figure
         23.35, where total load on MCC-1 as in the single-line diagram
         of  Figure 23.36 is
         3 x  10 h.p   =   30 h.p.
         4 x 5  h.p.   =   20 h.p.
         2 x  20 h.p.   =   40 h.p.
         2 x  40 h.p.   =   80 h.p.
         2 x  30 h.p.   =   60 h.p.
         1 ~100 h.p.   =   100 h.p.
         1 x  50 h.p.   =   50 h.p.
                           __
         Total            380 h.p. + spares and lighting load
         Note
         1  Lighting  loads  are  not  considered  for  the  following
            reasons:                                          Figure 23.36  Single-line diagram for MCC-1
   804   805   806   807   808   809   810   811   812   813   814