Page 804 - Industrial Power Engineering and Applications Handbook
P. 804

23/760  Industrial Power Engineering and Applications Handbook
         which  will  result  in an undercompensation  by 425  kVAr, or   kVAr = kVArl - kVAr,
         14.2%. It is therefore advisable to select the voltage rating of
         the capacitor units at almost the average voltage of the system,   and from Figure 23.29(a)
         which in the above case, will be
                                                              kVAr,
                                                              --    -  tan 4
          - 33 x 1.075 + 33 x 0.95  = 33.4 kV                   kW
                   2
         The capacitor banks may be designed for 33.4/ & kV.
           See also Example 23.1 to account for the voltage rise due
         to series reactor in case series  reactors are used.   :.  kVAr, - kVAr2 = kW(tan $,  - tan  $?) = kW . K
                                                                                             (23.17)
         23.12.2  Determining the kVAr rating           where K is a multiplying factor. For quick application of
         Consider  Figure  23.29(a),  where,  the  p.f.  of  a  power   this equation  and to simplify calculations, the factor K
         circuit is to be improved from cos qbl, to cos q&.  If kVArl   has been worked out for different values of cos #I and
         is the reactive component of power at p.f. cos &, which   cos & and reproduced in the form of Table 23.6.
         is to be improved to kVAr2, at p.f.  cos &, through the
         reactive power compensation, then the reactive component   Example 23.7
         of  power  compensated or kVAr  rating  of  the required   For a load of 75 kW, having a p.f. of 0.75, the capacitor rating
         capacitor banks                                to improve it to 0.95 can be calculated as follows:
                                                                 COS  $1  = 0.75
                                                                    $1  = 41.41"
                                                        and      tan  $1 = 0.882
                                                                 COS  $2  = 0.95
                                                        ..          & = 18.19"
                                                        and      tan & = 0.329
                                                        :.   tan  $1 -tan  & = 0.882 - 0.329
                                                        or          K = 0.553
                                                        (the same value can easily be determined from Table 23.6)
                                                        and the required rating of  capacitors,
                                                         kVAr = 75 x 0.553
                                                            = 41.5  kVAr
                                                          Say, 40 kbAr
                                                        See also Figure 23.29 (b).


                                                        23.13  Capacitor rating for an
         Figure 23.29(a)  Determining the kVAr rating of a shunt   induction motor
         capacitor
                                                        The selection of capacitor rating, for an induction motor,
                                      75 kW        V    running at different loads at different times, due either to
                                         c
                              Line current after        change  in  load  or to  fluctuation  in  supply  voltage,  is
                              cornwensation             difficult and should be done with care because the reactive
                                                        loading  of  the  motor  also  fluctuates  accordingly.  A
                                                        capacitor with  a  higher  value of  kVAr  than  the motor
                                                        kVAr,  under  certain  load  conditions,  may  develop
                                                        dangerous voltages due to self-excitation. At unity power
                                                        factor, the residual voltage of a capacitor is equal to the
                                                        system voltage. It rises at leading power factors (Figure
                                                        23.30). These voltages will  appear across the capacitor
                                                        banks when they are switched off and become a potential
                                                        source of danger to the motor and the operator. Such a
                                                        situation may arise when the capacitor unit is connected
                                                        across the motor terminals and is switched with it. This
                                                        may  happen  during an  open  transient  condition  while
                                                        changing over from  star to  delta,  or from one step to
                                                        another, as in an A/T switching, or during a tripping of
         Figure 23.29(b)  Reduction in line current after power factor   the motor or even while switching off a running motor.
         compensation                                   In all such cases the capacitor will be fully charged and
   799   800   801   802   803   804   805   806   807   808   809