Page 803 - Industrial Power Engineering and Applications Handbook
P. 803

Power capacitors: behaviour, switching and improvement of  power factor  231759
                                                                      -
                                                                  7-
                                                        :.  fl = 13.26 1-   0.4  kHz
                                                                 \I  129.19
                                                            = 13.26 x 0.0556 x  lo3 Hz
                                                            = 738 Hz

                              9
                    Insulation '2mmJL4 mm   '           which is substantially  dampened with  the  use of  additional
                                                        inductance,  and  is  only  slightly  more  than  the  switching
                                                        frequency  on  single  capacitor  switching as  worked  out  in
                                                        Example 23.3.
         (b) If we use two 25 mm2 cables as shown, then
            r1 = 7.8 mm or 0.78 cm                      23.1 2  Capacitor panel design
         and the number of turns that will be necessary:       parameters
                                 (
         42.93 x   = % x  N'  x  7.5  log,   7.5        Since this device is also associated with the same power
                     10              0.7788 x 0.78  -2)   system  as  a  switchgear  assembly,  it  should  generally
                                                        meet the  same specifications (Section  13.4) except for
                     4n
                   = - N'  x 7.5(10ge 98.77 - 2)        small  variations  in  operating  conditions  and  test
                        x
                     1 og                               requirements. Capacitors generate excessive heat  when
                     4n                                 in service. Installations employing large capacitor banks
                   =  ~   x N'  x 7.5 x 2.593           must therefore have a capacitor mounting structure suitable
                     109                                to dissipate heat freely and permit circulation of fresh air
         or      N = 13.26                              during  normal  operation.  To  achieve  this,  open-type
         Say, 13 turns                                  enclosures  are usually preferred when  it  is possible  to
                                                        house the panel in a separate room or mount the units on
         Switching frequency                            a structure in an open switchyard. It may also be provided
         As calculated above:                           with an expanded metal enclosure. Forced cooling within
                                                        the enclosure or the room where such banks are installed
                                                        is common practice to dissipate the excessive heat. For
                                                        more details refer to the following publications:
           C1  eq  = 5 x  9 x  120 x   F
         and C,  = C2 = 9 x  120 x  1 O-6F              IEC 6083 1 - 1 and 6093 1 - 1 for LT, and IEC 6087 1 - 1  and
                                                        IEC 60143- 1  for HT systems

                                                        23.12.1  Selecting the voltage rating of the
                                                               capacitor units
               - - ,  1   (5 x 9 x  120 x  10-6) + (9 x  120 x 10-6)
               -
                   \ i""   x  10+)(5  x 9 x  120 x  10-6)   must be taken  that during operation the voltage across
                 2n                                     When  selecting the  voltage of  the capacitor  units  care
                      3x5
                                                        the  capacitor units  does not fluctuate beyond *lo%.  If
               - lo3 I  6x3~5~10~                       this  happens  the  voltage  rating  of  the  capacitor  units
                 2rr  d 0.4 x 6 x 5 x 9 x  120          must  be  chosen  so  that  the  variation  across  the  units
                                                        under unfavourable operating conditions does not exceed
               = 13.26 kHz
                                                        *lo%.
         This will be the surge frequency of the switching circuit when
         the sixth capacitor is switched on a circuit that has five capacitor   Example 23.6
         units already switched. The improved value of this switching   If 3000 kVAr capacitor banks are required for a system of 33 kV
         frequency,  f;,  after the introduction of inductance 42.93 pH   + 7.5'4,  -5%  and the capacitors are rated for  34/?'3 kV then
         in each capacitor  circuit will become.        the output of the capacitors at nominal voltage will reduce to
               /y+L)x6
                                                        (g)' 3000 = 2826 kVAr
                                                              x
         L2e.q =          x  10-6H
                    5
                                                        which will  result  in an  undercompensation by  174 kVAr  or
                                                        5.8%. If the system voltage falls to, say, 31.5 kV during peak
                                                        load periods the rating of the capacitor  banks will fall further
         Cleq, = C1 eq = 5 x 9 x  120 x   F             and may render the system unstable,
                                                         Effective kVAr at 31.5 kV
           C, = C2 = 9 x  120 x   F
         Therefore the only change in the previous calculation is for   = [   x 3000
         LZeq, which is now substituted by (0.4 + 3L), i.e. (0.4 + 3 x
         42.93) or 129.19 for 0.4 in the numerator,      = 2575 kVAr
   798   799   800   801   802   803   804   805   806   807   808