Page 852 - Industrial Power Engineering and Applications Handbook
P. 852

24/806 Industrial Power  Engineering and Applications Handbook
                                                                                  400 kV transmission  or
                                                                                   132 kV distribution line
                                        I                Interrupter (
                                                                  d
                                                                \
                                       T        A/ D Transformer for                   Reactive power
                                       & V.T
                                                reactive power supply.
                                                Secondary at say, 11 kV
                                                                                        supply bus





             Line side reactor               Some fixed reactor
            to limit inrush current          to filter out sub-
           and suppress harmonics            harmonic components








                                  and feedback

                          0

        Note:  * Capacitors and reactors may be A connected to
              eliminate triple harmonics
         @ Thyristor switched capacitors     @)  Filter circuit to absorb harmonic currents caused by  TCR
         @ Thyristor controlled variable reactor (TCR)   @ (i)-A few fixed capacitor banks that may be normally ON.
           (it may also be a saturated  reactor)   (it)  Normally D connected. They are not grounded, when A connected
                  Figure 24.31  Scheme for a reactive  power control showing combined  TSC,,  TCR,  and fixed  capacitors


          also generate capacitive reactive power. Refer to Figure   Nores
          24.33 for more clarity.                      I   Reactive control is also possible through synchronous condensers.
                                                         As  they  rotate, the rotor  stores kinetic energy which tends  to
                                                         absorb sudden fluctuations in the supply system, such as sudden
          Consider a noymal load line (1) (Figure 24.32) having   loadings.  They  are. however,  sluggish  in operation  and  very
        the initial operating point  at (a). On a  disturbance, the   expensive compared to thyristor controls. Theii rotating masses
        load line shifts to (2) and the operating point to (b). The   add inertia, contribute  to the transient oscillations  and add to
        TCR would respond and some inductive reactance (X,)   the fault level of the system. All these factors render them less
        will be shed to raise the content of Xc. The load line will   suitable  for  such  applications. Their  application  is  therefore
        become less inductive and more capacitive to help the   gradually disappearing.
         voltage rise to point (c) within  one cycle. If the voltage   2   Reliability  of  shunt  or  series  power  capacitors  is  of  utmost
                                                          importance  for the  security of  the  system on  which  they  are
         is  still  below  the preset  value,  some capacitors can be   installed. Their  failure  may  disturb  the  system or result  in  a
         switched ON either electromechanically or through TSCs,   system outage.
         depending upon the system adopted. The delay at point   3   Generally, SVCs are designed for I1 or 33 kV and connected to
         (c)  will  depend  upon  the  method  of  switching  of  the   a higher voltage system through a dedicated transformer through
         capacitor banks. The voltage will now jump to point (d)   the tertiary of  the  main  transformer. Figure 24.33 illustrates a
         and  final  correction  is  achieved  up  to  point  (e).  The   typical SVC system using a dedicated transformer.
         sequence a-e  would complete in less than two cycles if   4   Since reactive  controls  are normally  meant  for  large  to  very
                                                          large installations, the practice so far has been to use thyristors
         all the components are thyristor switched. The sequences   only for such applications. With  the advent of  IGBTs, smaller
         from a-b-c-d-e can be reduced to a-b-e allowing a little   installations can now be  switched through IGBTs.
         over- or undershoots from c to d.
   847   848   849   850   851   852   853   854   855   856   857