Page 850 - Industrial Power Engineering and Applications Handbook
P. 850

24/804  Industrial Power Engineering and Applications Handbook

           is quick and matches the fast-changing load parameters
           of the power network at the receiving end. They are
           capable of maintaining a near-constant voltage profile
           at all times at the receiving end. The correction achieved
           is accurate and smooth, besides being extremely fast
           and free from surges. They may be installed at strategic
           locations along the line or at the receiving end. The
           selection of location is an important aspect to optimize
           the size of compensator and a more efficient voltage
           regulation.
             A fast  VAr  control  is  achieved through  thyristor
           switching,  which  by  itself  is  capable  of  a  stepless
           variation.  But  switching  of  capacitors,  which  are
           switched in banks, is not stepless. The SVCs may be
           of the following types.

        24.10.1  Thyristor-switched capacitor banks          Figure 24.28(a)  Switching instants for a TSC
               (TSC)
         Thyristor-switched capacitor banks are normally connected
         in parallel with several banks of shunt capacitors to control
         the system voltage. Feedback sensors and controls monitor
         the voltage level. When the voltage swings to either side
         of the preset value, a few banks are switched in or switched
         out. This is illustrated in Figures 24.28(a) and (b). Point
         a indicates the operating point under normal conditions.
         During a load variation or disturbance the voltage dips
         and the operating point shifts to 6. With the use of TSC,
         the  load  point  is  shifted  back  to  c.  Since  the  control
         is in steps, it may be coarse. The steps may be limited to
         save on the cost of thyristors. This step change in voltage
         can be smoothed and a stepless reactive control achieved
         with  the use of  a TCR (thyristor-controlled reactor)  in
         parallel and operating it with the TSC banks in tandem.
         Such a scheme can be tailored to suit even the smallest
         reactive need of a system. The combination can be termed
         hybrid compensators. One such scheme is illustrated in
         Figure 24.3 1 and discussed later, in more detail.
          In TSCs the thyristors are used in anti-parallel to switch
         a capacitor bank ON or OFF but without any phase angle              1, -
         control. A TSC therefore does not by itself generate any
         harmonics, unlike a TCR.
                                                       Figure 24.28(b)  Improvement in loading by use of a TSC
                                                       compensator
         24.10.2  Thyristor-controlled reactors (TCRs)
         These consist of two oppositely poled thyristors, as shown
         in Figure 24.29 and conduct on alternate half  cycles at
         the fundamental frequency. Reactors may be switched or   reactors and the thyristors are connected in delta, triple
         phase angle controlled. Three-phase SVCs can indepen-   harmonics can be eliminated and filter circuits would be
         dently control each phase and the TCR can be used  for   necessary  only  for the remaining  harmonic  quantities.
         phase  balancing.  When  a  phase  angle  is  controlled,  a   Various combinations of thyristor circuits are possible to
         stepless reactive power control can be achieved, except   obtain a desired phase displacement between the voltage
         for generation of harmonics during the control process.   and the current (cos $) and hence suppress the various
         The gate control at peak voltage (a = 90") can allow full   harmonic contents present in the system. (Section 6.13
         conduction of the reactor. The conduction can be controlled   provides more details on this.) See also the further reading
         by  varying  the  gate  angle,  a. For  example,  partial   at the end of this chapter.
         conduction is possible with a between 90" and 1 SO", but   The number of thyristors in series, each selected for
         a from 0-90"  is  not  used,  as  then  the  circuit  would   an impulse voltage of a little less than the impulse voltage
         produce  asymmetrical  currents  with  d.c.  components.   withstand level of  the terminal equipment (Table  11.6)
         The effect of  increasing the gate angle is to reduce the   can effectively limit the switching overvoltages within
         harmonic components of the current, and hence the power   desired safe limits. Then connecting them in anti-parallel
         losses in  the thyristor controller  and the reactor.  If  the   will  mean that the voltage will be forward for either of
   845   846   847   848   849   850   851   852   853   854   855