Page 890 - Industrial Power Engineering and Applications Handbook
P. 890

Protection, maintenance and testing of capacitor units  26/841
         capacitance of the test unit may be measured before the   flashover  should  be  observed.  The  variation  in  the
         discharge test and after the voltage test. The capacitance   capacitance value as measured before and at the end of
         values thus measured  should not be exceeded  by  more   the test  should not vary by more than  3%. The capacitor
         than  2% or breakdown  of  an element or blowing of  an   unit  should  withstand  the  voltage  test  between  the
         internal fuse.                                terminals  and the  container  as  stated in  test  (4) above
                                                       and the scaling test  as in test  (6) under routine tests.
         (7) Partial discharge test (applicable to HT units)
         There are invariably voids that will appear in an insulating   (IO) Self-healing test
         system  as a  matter of  process,  irrespective of  the type   This test  is applicable to LT  capacitors only.  which  are
         and procedure of impregnation adopted. as discussed in   the  self-healing  type.  The  capacitor  is  subjected  to  a
         Section 9.6.1. For all practical purposes, a dielectric system   voltage  of  2.15  V,,  for  10 seconds.  If  fewer  than  five
         may therefore be considered to be an imperfect capacitor.   breakdowns occur during this time.  the  voltage  may be
         All such voids may cause internal discharges and lead to   increased slowly until it reaches 3.5 times its rated value,
         erosion  and ultimate failure of  the dielectric  under the   or  five  breakdowns,  whichever  happens  first.  If  five
         effect of  the  applied  voltage.  The applied voltage  may   breakdowns have still not occurred, the test is continued
         be fluctuating too. aggravating the situation. This test is   until they do. The capacitance measured before and after
         conducted to check the condition and suitability of  the   the test should show no significant change.
         dielectric used  to perform the required duties in service
         without causing an undue discharge (ionization). It  is a   (1 I) Destruction test
         means of detecting defects in the insulating system of a
         capacitor unit and is complementary to a dielectric test.   This test  is  also applicable to  LT  capacitor  units  only.
          To perform this test, the rated voltage may be applied   The basic  objective is  to  establish that  the  failure of  a
         long enough for thermal equilibrium to be achieved. Then   unit is within a safe zone and is not accompanied by the
         a test  voltage of twice the rated voltage is applied only   risk of  a violent explosion or fire.
         once for one second. The voltage is then reduced to  1.2
         times the  rated  voltage and maintained for  10 minutes   These are only brief descriptions of the recommended
         and then it is raised  again to  I .5  times the rated  voltage   tests and their procedures on a completed capacitor unit.
         for 30 minutes. During the last 10 minutes, the discharge   For more details refer to the table of Standards provided
         under such conditions  should be less than  SO  pc (pico-   at the end of the chapter.
         coulombs). The capacitance  should  be  measured  both
         before and after the test. The change in capacitance should   26.3.3  Checking field operating conditions
         not exceed 2%.                                On  larger  installations, particularly.  it is  recommended
          One will appreciate that such tests are no guarantee of
         the minimum life of a capacitor unit. Moreover, it is not   that  the  actual  operating  conditions  he  checked  and
                                                       compared  with  the  assumed  conditions  for  which  thc
         expected  that  such  tests  can  predict  the  future  of  the   capacitor units were designed to ensure that thcy do not
         capacitor units. They can, at best, suggest the compliance   differ by more than the permissible limits. This is because
         of the test requirements which should ensure a reasonably   a  capacitor  is  highly  susceptible  to  some  operating
         prolonged operating life of the capacitors, as envisaged.   conditions such as fluctuations in  voltage  and harmonic
         These tests do provide feedback to the manufacturer on   contents in the system. An excess of any of these or both
         the quality of the dielectric and the process of insulation   V and V, may shorten the life of the capacitor units and
         adopted and if  any improvements are required.
                                                       cause frequent failures of  individual units.  It  may  also
                                                       lead to overvoltages across the units and incrcasc harmonic
         (8) Endurance test  (process test for HT capacitors)   contents. All this may cause failure of the capacitor units,
         This is an alternative to the ageing test and is applicable   leading to even a cascade failure. increasing the unbalance
         for shunt capacitors  of  1000 V  and above.  It  is  an  in-   in  voltage and kVAr  across each phase  and destabilize
         house  process  test  and  is  carried  out on  the  capacitor   the cntirc capacitor nctwork.
         elements before they are assembled into a capacitor unit   The effect of voltage and voltage fluctuations can he
         to ascertain their dielectric stability against repeated over-   checked through the capacitor line current. I,, which is a
         voltages. For the test procedure refer to IEC 6087 1-2.   measure of the capacitance C of the capacitor units. The
                                                       capacitor current must correspond to the designed (rated)
        (9) Ageing test  (applicable to LT units)      current plus the permissible variation.  A higher current
                                                       than this would mean a voltage variation or the presence
        This test  is conducted to estimate the working life of  a   of  harmonics  in  the  system or both. While the  voltage
        capacitor. Briefly. the test can be conducted in three stages   may  be  measured  through  a  voltmeter and  the  current
        as follows:                                    through  an  ammeter  in  the  three  lines,  the  harmonics
         (a) The  capacitor is  energized  at  1.25 times  the  rated   content may be checked by an oscilloscope. If the actual
            voltage for 750 hours.                     operating conditions differ from the designed parameters
         (b) It is then subjected to  1000 discharges.   by  more than  is permissible.  suitable measures  will  be
         (c) After test  (b). the test  in  (a) is repeated.   essential  to restore  the  operating conditions  within  the
                                                       permissible  limits.  say, by  providing  series reactors  or
          On conclusion of the test no permanent breakdown or   filter circuits in the system as discussed alrcady.
   885   886   887   888   889   890   891   892   893   894   895