Page 909 - Industrial Power Engineering and Applications Handbook
P. 909

28/860 Industrial Power Engineering and Applications Handbook
























                       Figure 28.2(a)  Low rating LT bus duct















                          Non-magnetic or   Barriers (same metal  Clamps (same metal
                          magnetic enclosure   as the enclosure)   as the enclosure)

                                     Figure 28.2(b)  A segregated phase bus system

         melallic barriers provide the required magnetic shielding   unbalance between the three phases as discussed in Section
         and isolate  the  busbars  magnetically  from each  other,   28.8.2 and enhance the electrodynamic forces that may
         rather like an isolated phase bus system (IPB). For more   lead to a phase-to-phase fault at higher rated currents.
         details see Section 3 1.2. The enclosure can be of MS or
         aluminium and the barriers can be of the same metal as   Application
         the enclosure. The purpose of providing a metallic barrier
         is not only to shroud the phases against short-circuits but   They are generally used for higher ratings, 2000 A and
         also to reduce the effect of proximity of one phase on the   above, on all voltage systems. They are, however, preferred
         other by arresting the electric field produced by the current-   on an HT rather than an LT  system for reasons of cost,
         carrying  conductors  within  the  barrier  itself.  It  now   such as between a unit auxiliary transformer (UAT) and
         operates  like  an  enclosure  with  an  interleaving   its switchgears and a station transformer and its switch-
         arrangement (Section 28.8.4) balancing the fields produced   gears  as  in  a  power-generating  station  and  shown  in
         by  the conductors  to  a great  extent  and  also allowing   Figure  13.21.
         only a moderate field in the space, as in an IPB system
         (Section  31.2).  The enclosure  losses  with  such  an   Nute
         arrangement may fall in the range of 6M5% of conductors   For  such  ratings,  enclosure of  non-magnetic  material  alone  is
                                                       recommended due to high  iron  losses in a magnetic material.
         in  case  and  30-35%  in  aluminium  enclosures  for  all
         voltage  systems 3.3-1 1 kV  and  current  ratings  above   Nominal current ratings
         3000A and up to 6000A or so. Only aluminium enclosures
         should be preferred  to  minimize  losses  and  enclosure   These will  depend upon  the application. The preferred
         heating. The effect of proximity is now almost nullified   ratings may follow series R-10 of IEC 60059, as described
         as is an imbalance in the phase reactances. An unbalance   in Section 13.4.1(4). They may increase to 6000 A or so
         in  the reactance is otherwise responsible  for a  voltage   depending upon the application.
   904   905   906   907   908   909   910   911   912   913   914