Page 913 - Industrial Power Engineering and Applications Handbook
P. 913

28/864  Industrial Power Engineering and Applications  Handbook
        Table 28.1  Momentary peak (maximum r.m.s.)  current ratings, asymmetrical, for switchgear and metal-enclosed bus systems,
        based on ANSI-C-37/20C

        Nominal  voltage   Rated current (Ir)   Non-begregated phase  cjstenz   Segregated phase sxstem   Icolrited phase osteiii
        kV(Km.s.)     A"              kAh                   kA"                kA
                                            ~           ~~~     ~                            ~~
        0.6           I600            75                    -                  -
        0.6           3000            100                   -                  -
        0.6           4000 to 6000    I50                   ~                  -
        4.16-13.8     1200 to 3000     19 to 78             -                  -
        14.4          I200 to 20 000   -                    60 to  190         To match with the iating
                                                                               of  the connected
                                                                               interrupting  device
        23-34.5       1200 to 20 000   58                   60 to  190
                                                                           ._             ~~
        a (i) These values are based for a system, pertaining to series  I1 and a frequency of 60 Hz.
        (ii)  For systems pertaining to Series I  and a frequency of  50 Hr, values furnished in Section  13.4.1(4).  would apply.
         The peak value is a function of fault level Section 13.4.1 (7), ydbk 13.1 I. Which in turn, is a function of size and impedance of the feeding
        source, such as a transformer or a generator, Section 13.4. I (S), Table  13.7. The values prescribed  in the above table are thus based on thehe
        parameters.

        28.4  Short-circuit effects                   circuit release\ of a current limiting  interrupting device the cut-off
                                                      time may be extremely low, of the order of less than one quarter of
                                                      a cycle, i.e. < 0.005 second (for a SO  Hz system) (Section  13.5.1)
        (To  determine  the  minimum  size  of  current-carrying   depending upon  the size and the characteristics  of the fuse? or the
        conductors and decide on the mounting arrangement).   interrupting device and the intensity of the fault current. Any level
        A short-circuit results in an excessive current due to low   of fault for  such a  system would be of  little consequence, a5 the
        impedance  of  the  faulty  circuit  between  the  source of   interrupting  device would isolate  the circuit  long before  the fault
        supply  and  the  fault.  This  excessive  current  causes   current reaches its first peak. This is when the fault is downstream
        excessive heat  (= IC', . R) in  the current-carrying  con-   of the protective device. Refer to Example 28.1  below.
        ductors and generates  electromagnetic  effects  (electric
        field) and electrodynamic forces of attraction and repulsion   Example 28.1
        between  the  conductors  and  their  mounting  structure.   Since the heating effect  = I$  . t
        These forces are distributed uniformly over the length of   therefore  heating  effect  of  a 50  kA fault  current  for  0.005
                                                      second = 50'  x 0.005, compared to the heating effect of an
        conductors and cause shearing forces due to the cantilever   equivalent fault  current  I,,  for  1 second,  i.e.  -
        effect as well as compressive and tensile stresses on the                          . 1
        mounting structure. The effect of a short-circuit therefore
        requires these two very vital factors (thermal effects and   or  /& = 50'  x 0.005
        electrodynamic forces)  to be taken  into account  while   i.e  I,,  = 50 x liooos
        designing the size of the current-carrying conductors and
        their mounting structure. The latter will include mechanical   or 3.5 kA only
        supports, type of insulators and type of hardware, besides
        the longitudinal  distance between  the supports and the   Thus to design a system protected through HRC fuses
        gap between phase-to-phase conductors.         or a current limiting device for a higher fault level than
          The electrodynamic forces may exist for only three or   necessary will only lead to overprotection and the extra
        four cycles (Section 13.4.1 (7)), but the mechanical system   cost of the current-carrying.system, switching equipment
        must be designed for these forces. On the other hand, the   and power  cables. An  individual device or component
        main  current-carrying  system  is  designed  for  the   and its connecting links in such cases may therefore be
        symmetrical  fault  current, I,,  (Table  13.7) for  one or   designed for a size commensurate to its current rating.
        three seconds according to the system design. For more   See also Section  13.5.1.
        details refer to Section 13.5.                  Below we discuss the thermal effects and the electro-
          The fault level, which is a function of  the size of the   dynamic  forces  which  may  develop  during  a  fault  to
        feeding transformer, is generally considered to last for   decide on the correct size of the conductor and its suppor-
        only one second, as discussed in Section 13.4.1(5), unless   ting system.
        the system requirements are more stringent. This duration
        of one second on fault may cause such a temperature rise   28.4.1  Thermal effects
        (not the electrodynamic forces), that unlcss adequate care
        is  taken  in  selecting  the  size  of  the  current-carrying   With normal interrupting devices the fault current would
        conductors, they may melt or soften to a vulnerable level   last for only a few cycles (maximum up to one or three
        before the fault is interrupted by the protective devices.   seconds, depending upon the system design). This time
                                                       is too short to allow heat dissipation from the conductor
        Nute                                           through radiation or convection. The total heat generated
        When the circuit is protected through  HRC fuses or built-in short-   on a fault will  thus be absorbed by  the conductor itself.
   908   909   910   911   912   913   914   915   916   917   918