Page 922 - Industrial Power Engineering and Applications Handbook
P. 922

28/872 Industrial Power Engineering  and Applications Handbook
       Table 28.4  Clearances for enclosed, indoor air-insulated busbars   each phase and neutral, wherever the bus enclosure passes
                                                      through  a  wall.  The  bushings  may  be  of  SMC/DMC/
       Rated  voltage   Minimum clearance   Minimum  c1prrranr.r   FRP or porcelain for LT  and epoxy  compound for HT
                     to ground  in air   between phases in uir   systems. They may be fitted at the crossovers so that the
       kV  (Km.s.)   mni             mm               indoor bus is sealed off from the outdoor one. The bus
                                                      conductors will  pass through the bushings. The HT bus
       Up to 0.415    16              19              conductors may be moulded with the epoxy bushings, as
        0.6           19              19
         3.3         51               51              illustrated in Figure 28.1 l(b), similar to bar primary CTs
        6.6          64               89              (Figure 15.14) to make the joint airtight. In LT a simpler
        11           76              121              method is found by providing glass wool in the part that
        15           102             165              passes through the wall as illustrated in Figure 28.1  l(a).
        22           140             24 1
        33           222             356
                                                      28.5.4  Excessive vibrations and seismic effects
                                                      These will require a more robust  enclosure, similar to a
        Table 28.5  Creepage distances for enclosed  indoor ail   switchgear assembly. For details refer to Section 13.4.2.
        insulated busbars as in  BS 159
        Ruted  voltage  Minimum creepage   Minimum creepage   28.6  Other design considerations
                  distance to ground   di.mnce between phases
        kV (rm,s.)   in air mm     in uir               Size of enclosure
        Up to 0.415   19                                Voltage drop
         0.6       25              1                    Skin and proximity effects
         3.3       51
         6.6       89                Minimum  50% more
        11        121                                 28.6.1  Size of enclosure
        15        152
        22        203              I                  The  enclosure of  the  bus  system  provides  the  cooling
        33        305                                 surface  for  heat  dissipation.  Its  size has  an  important
                        ~.  ~                         bearing  on  the  temperature  rise  of  conductors  and
        Notes                                         consequently their current-carrying capacity. The enclo-
        I  The above figures are only indicative, and may be considered as   sure effect and the ventilating conditions of the surroun-
          a minimum for a bus system that is dry and free from dust or any   dings in which the enclosure is installed should thus be
          contamination,  which  may  influence  and  reduce  the  effective   considered  when  designing  a  bus  system. The ratio of
          creepage over time. These creepages may be increased for damp
          dirty or contaminated locations.            the area of the current-carrying conductors to the area of
        2  For clarification and more details refer to BS  159.   the  enclosure  will  provide  the  basis  to  determine  the
                                                       heat dissipation effect. Table 28.6 suggests the approximate
        Common to both tables                          dissipation  factors  that  can  be  considered  as  likely
        1  The above clearances and creepage distances are for altitudes of   deratings  for  a  bus  system  under  different  conditions.
          up to 2000 m for LT and  1000 m for HT systems.
        2  For higher altitudes than this, these distances should be increased   See also Example 28.12.
          by  at  least  1%.  for every  100 m rise in  altitude.
        3  Voltages  higher .than  above, are not  applicable  in  case  of  bus   28.6.2  Voltage drop
          systems.
                                                       The voltage drop across a bus system should be as low
                                                       as possible and generally within 1-2%  of the rated voltage.
        28.5.3  Atmospheric conditions                 This  criterion  will  generally  be  applicable  to  a  high-
                                                       current LT system. On HT and low LT current-carrying
        The same conditions  would  apply  as for a  switchgear   systems, this drop may be quite low. The length of a bus
        assembly  (Section  13.4.2).  Unlike  a  controlgear  or  a   system, in most of applications, may not be long enough
        switchgear assembly, a bus system may be required to be   to cause a voltage drop, IZ, to be taken into consideration.
        partly located outdoors. This is true for most installations,   It may be the connection from the incoming transformer
        as the switchyard is normally located outdoors as is the   to the  main  receiving  switchgear or the busbars  of  the
        feeding transformer, while, the switchgears are located   main switchgear assembly itself. Applications requiring
        indoors, to which the bus system is connected.   extra-long  current-carrying  conductors,  however,  may
          In such conditions, it is important that adequate care   have large impedance and may cause high voltage drops,
        is  taken  to  construct  the  bus  enclosure to  weather  the   of the order of 3-5%  and even more. When so, they may
        outdoor conditions such as by providing a canopy on the   affect the stability of the system as well as the performance
        top and special paint treatment on the outdoor part. It is   of  the  connected  load.  This  is  illustrated  in  Example
        also recommended to seal off the indoor from the outdoor   28.9. To  ascertain the  voltage  drop in  such cases  it  is
        part to prevent the effect of rainwater, dust and temperature   essential to determine the actual values of the conductor’s
        and  other  weather  conditions on the  indoor part.  This   own resistance, reactance and the impedance under actual
        can be achieved by  providing seal-off  bushings, one on   operating conditions.  It  may be  noted that  reactance is
   917   918   919   920   921   922   923   924   925   926   927