Page 984 - Industrial Power Engineering and Applications Handbook
P. 984

An  isolated phase bus system  31/929
         31.1  An isolated phase bus (IPB)              plant  is  illustrated  in  Figure  31.2(a) and  (b). It  may
               system                                   comprise the following sections.
                                                        31.1.1  Main run and auxiliary feed lines
         In  this  construction  the  conductors  of  each  phase  are
         housed in a separate non-magnetic metallic enclosure to   1  From generator phase terminals to the lower voltage
         isolate them completely from each other with the following   side of  the  GT. This section may partly  be  indoors,
         advantages:                                      connecting the generator inside the turbine room and
                                                          partly outdoors, connecting the GT in the transformer
          I  It eliminates phase-to-phase faults.         yard.
         2  It  eliminates the  proximity  effect  (extra forces  and   2  A  generator  neutral  bus  to  form  the  generdtor  star
            heating)  by  providing  a  magnetic  shielding  to  the   point.
            \upporting and metallic structures in the vicinity.   3  Tap-offs with tee joints from the main  run to the two
         3  It  reduces  the  proximity  effects  between  the  main   UATs.
            current-carrying conductors of the adjacent phases to   4  Sometimes  from  UAT  secondaries  to  the  unit  HT
            almost  zero  due to  magnetic  shielding,  on  the  one   switchgears.
            hand. and large centre spacing, on the other.   5  If the GT is made of three, single-phase transformers,
         4  It provides complete protection for operating personnel   an  interconnecting IPB will  be  required  to form the
            t'roin high touch or step voltages (for details on contact   delta as illustrated in  Figure 3 I .?(b).
            voltages.  see Section 22.9) across the enclosure and
            the  metallic  structures caused  by  parasitic  (electro-   31.1.2  Instrumentation and protection
            magnetic) currents.                               connections
         5  The bu\ system is are easy to handle, bend and install.
                                                        Since an IPB forms an important integral part ofa power-
           This  is  used  for  HT  systems  of  very  large  ratings.   generating  station, with  it  are  associated  a  number of
         Since it  is a more expensive arrangement  it is normally   metering and protective devices such as CTs, VTs and
         preferred only for crirical  installations such as a power   generator grounding  system. Below  we  identifiy  inter-
         generating station. where  it  has  to  carry  large  to  very   connections that may be required  to connect these CTs
         large currents due to high ratings of the generating units.   and VTs while installing an  IPB  system.
         In a thermal power plant it is used between the generating
         unit (G) and the generator transformer (GT) and the unit   I  Removable links for easy mounting and maintenance
         auxiliary  transformers  (UATs)  as  well  as  sometimes   of CTs for metering and protection. typically as follows.
         between the UAT and the unit HT switchgear as illustrated   For each phase in the main lines between the yenerator
         in Figure 13.2 1 (redrawn in Figure 3 1.1 for more clarity).   and the GT,
         A typical layout of such a bus system in a thermal power   1  CT for metering



                                        To  switch yard
                                                                    .
             Transformer           Generator
                                   transformer
                                                                               - Three  phase  two  wind
                          Tap-off
                         connection  1       ~   Tee joints   Tap-off            ing transformer (UAT)
              Outdoor
              installation                                                     - Three  phase  two  wind-
                                                                                ing transformer with ON
                                                                                load tap changer (GT)

                                 Unit bus duct                                  Circuit breaker



                                   chamber
                              J HT breaker
              Indoor                                         H T  breaker
            installation     (  33 kV/ll kV/
                              I  66kV

                                          Figure 31.1  Application  of  an IPB
   979   980   981   982   983   984   985   986   987   988   989