Page 202 - Solutions Manual to accompany Electric Machinery Fundamentals
P. 202

ylabel('\bf\tau_{ind}');
                 title ('\bfInduction Motor Torque-Speed Characteristic');
                 grid on;
                 The resulting plot is shown below:



































          6-30.  Answer the following questions about a 460-V -connected two-pole 100-hp 60-Hz starting code letter F
                 induction motor:
                     (a)  What is the maximum current starting current that this machine’s controller must be designed to
                     handle?

                     (b)  If the controller is designed to switch the stator windings from a  connection to a Y connection
                     during starting, what is the maximum starting current that the controller must be designed to handle?
                     (c)  If a 1.25:1 step-down autotransformer starter is used during  starting,  what  is  the  maximum
                     starting current that it must be designed to handle?

                 SOLUTION
                 (a)  Starting code letter F corresponds to a 5.00 – 5.60 kVA/hp, so the maximum starting kVA of this
                 motor is
                                S   100 hp 5.60       560 kVA
                          start
                 Therefore,
                                 S      560 kVA
                         I start                 703 A
                                3  T    3  V  V 460

                 (b)  The line voltage will still be 460 V when the motor is switched to the Y-connection, but now the
                 phase voltage will be 460 /  3  = 266 V.

                 Before (in ):