Page 220 - Instrumentation Reference Book 3E
P. 220

204  Microprocessor-based and intelligent transmitters

            before  onward  transmission.  For  example,  the   very  useful.  With  FOUNDATIONTM Fieldbus
            primary  sensor  signal may  have  a  known  non-   there  is  a  move  towards  further  field-mounted
            linear  relationship  with  the  measured  variable.   computation  and data reduction  with  gas mass
            The most common examples of this are resistance   flow calculations; for example, being carried out
            temperature  detectors,  thermocouples,  and  the   in  situ.  In  a  control  system  based  on  the
            square law inherent in the relation between flow   FOUNDATION  Fieldbus  protocol  such  as
            rate and differential pressure developed across an   Smar’s  SYSTEM302,  the  regulatory  control  is
            orifice  plate  or  other  head  producing  primary   primarily  performed  by  the  Fieldbus  control
            element. In addition, however, actual calibration   valve positioner.  such as the Smar FY302.
            information for an individual transmitter may be
            stored in memory and used to enhance the accur-
            acy of the output signal.                 13.4.1.3  Expression  oj. tlze inensuveinent in
                                                      engineering  units
              In those cases where the measurement  system
            comprises two  discrete units,  such as a primary   There  are  several  ways  in  which  this  can  be
            sensor and a separate transmitter which incorpor-   effected.
            ates  the  computation unit,  provision  would  be
                                                       (i)  Adjusrineizt of the 4-20  n7A range. Using the
            made to enter the constants of the primary sensor   span and zero setting functions,  it is possible to
            into the computation  unit  of  the transmitter,  so   set the values for the measured quantity at which
            that either unit could be changed.        the output shall be 4 mA and 20 mA respectively.
              As well as these purely mathematical manipu-
            lations  of  the  original  data,  auxiliary  internal   This  is  particularly  useful  in  matching  existing
                                                      recorders or indicators.
            measurements  may be made  of  line pressure  or   (ii) Digital conznnmication.  It is generally pos-
            temperature to permit the output to be corrected   sible to set the scaling of an instrument so that the
            for the effect of these quantities on the transmit-
            ter’s performance. That is a separate activity from   measured variable (e.g.. flow rate) shown on the
                                                      hand-held communicator or on the operator dis-
            correcting the resulting measurement for changes
            in the fluid properties with temperature  or pres-   play  appears in the desired or specified units  of
            sure,  although  some  instruments  may  permit   measure, with the abbreviation for the unit along-
                                                      side (e.g., 7.5 kg/s). This can be set quite independ-
            access to these  auxiliary measurements  over the   ently  of  the  scaling of  the  4-20mA  signal and
            communication  link  so that  they could  be  used   avoids  calculation  errors  by  the  operators  con-
            externally for that purpose.
              The provision  of linearized and corrected  sig-   verting from percentage flow rates to engineering
            nals  to  a  control  system  means  that  it  is  not   units.
                                                       (iii) Pulse oirtpurs for totalization. Many flow-
            burdened with the need to perform these compu-   meters  have  provision  for  a  pulse  output  at  a
            tations and the type or make of transmitter fitted   frequency  proportional  to  the  flow  rate.  These
            in a particular location is of no significance to the
                                                      pulses may be counted externally or in the instru-
            control  system,  since  it  can  assume  that  the   ment  itself to provide  a  totalized  flow read-out.
            received signal will always be linearly representa-   The scaling of this output can be chosen so that
            tive of the process parameter.
                                                      the interval  between  pulses represents  a  specific
                                                      volume or mass of fluid. This feature is useful in
            13.4.1.2  Inclusion of controljimctions  arid orlzer   that  it  permits  simple  counters  to  be  used  to
            algoritkins                               record  the total and permits a suitable pulsating
            The  microprocessors  used  in  microprocessor-   rate to be chosen for electromechanical counters.
            based  or  intelligent  transmitters  are  more  than   (iv) Frril-safe j’krures. All the intelligent flow-
            capable of carrying out the relatively simple com-   meters provide some internal diagnostic routines
                                                      and  are  capable  of  flagging problems.  In  some
            putation involved in on-off,  two-term,  or three-   instruments  it  may  be  possible to  specify what
            term  control,  and  some instruments  now  avail-
            able  provide  this  feature. Tuning  of  the loop is   should happen  to the output under certain fault
            then implemented using the communication link.   conditions, e.g., “go to 3.6mA” or “go to 21 mA.”
              Until  the  advent of  FOUNDATIONTM Field-   These sections are so application-specific that no
            bus, relatively  few  manufacturers  were  offering   general conclusion can be drawn. In  some cases it
            transmitters with this feature so they were there-   may be important to stop the process; in others this
            fore  rare  in  large  and  complex  plants,  which   may not be feasible and an assumed value for the
            required  more  complex  and  sophisticated  con-   process parameter may have to be substituted dur-
            trol than could  be provided  in early transmitter   ing failure.
            mounted devices. For small self-contained appli-   There were initially some fears that these more
            cations  the  built-in  PID controller  in  the  Smar   complex instruments would fail more frequently
            LD301  pressure  transmitter  has  proved  to  be   than  their  analog  counterparts.  However,  more
   215   216   217   218   219   220   221   222   223   224   225