Page 299 - Modern Control of DC-Based Power Systems
P. 299

258                                 Modern Control of DC-Based Power Systems


          disconnection of LRC 3 .In Fig. 7.7 it is seen that the response has a faster
          settling time and the peak to peak oscillation is larger than in the load
          connection case. The reason for the faster settling time lies in the load
          factor which is 0.5, smaller compared to 0.66 load factor in the step
          increase test case.
             The LSF exhibits, in Fig. 7.8, a transient behavior which is less
          smooth than during the step increase. The reason is that the compensa-
          tion and linearization of the nonlinearity was split over three converters
          but only two converters need to fulfill the task without an update of their
          compensation coefficients. This shows a remarkable result in term of
          robustness that such a drastic change from the model assumption can be
          withstood by the LSF. Similar to Fig. 7.6, also in Fig. 7.8 an oscillation
          can be detected that remains in steady state but is bounded to
           6 0:2280 kV which is equal to 3.986% of the averaged steady-state
          value. The system under the control of the LSF is consequently BIBO
          stable.
             The experimental results can be summarized in the following way:
          The corresponding transient response parameters are presented and sum-
          marized in Table 7.2 considering that:
          •  Settling time, over-, and undershoot values are based on switched
             quantities.
          •  Overshoot percentages are calculated based on mean values of steady-
             state voltages.
          •  Each controller has a different base voltage, which is due to the
             involved droop sharing difference.




          Table 7.2 Summary of Shipboard Power System Scenario
                                      Scenario 1
          Power sharing (%)           33/33/33
          Generation power (MW)       60
          Base load (MW)              20
                                      LQG                   LSF
          Mean (kV)                   5.85                  5.72
          Load step (MW)              125                   125
          Generation loss (MW)                   220                   220
          Settling time (ms) (5%)     15.9       5.6        30.9       36.3
          Undershoot (%)              9.87       9.58       13.4       13.7
          Overshoot (%)               3.10       4.77       6.85       11.8
   294   295   296   297   298   299   300   301   302   303   304