Page 45 - Power Electronic Control in Electrical Systems
P. 45

//SYS21/F:/PEC/REVISES_10-11-01/075065126-CH002.3D ± 35 ± [31±81/51] 17.11.2001 9:49AM







                                                             Power electronic control in electrical systems 35

                      Table 2.3 Font and symbol conventions
                      Type                    What is meant          Examples

                      Lower-case italic       instantaneous values   u, i
                      Upper-case italic       RMS values or DC values  V, I
                                              Resistance, reactance, and  R, XZ
                                              impedance magnitude
                                              Inductance and capacitance  L, C
                      Upper-case boldface roman  Phasors             V, I
                                              Impedance              Z
                                              In handwritten work, you can't really use boldface, so use a bar
                                              or arrow or tilde ± preferably over the symbol, e.g. ~ V, V, ~ V.
                      Subscripts can be roman or italic; it is a matter of style
                      In three-phase systems, various conventions are used for the subscripts used to denote the three phases.
                      In Europe (particularly Germany): U, V, W. In the UK: R, Y, B (for red, yellow, blue), or a, b, c. In the
                      United States: a, b, c or A, B, C. You will also see 1, 2, 3 used: this seems an obvious choice, but if
                      you are working with symmetrical components these subscripts can be confused with the positive,
                      negative, and zero-sequence subscripts 1, 2, 0 (sometimes ‡,  , 0). The best advice is to be very careful!
                      Never confuse phasor values with scalar values!

                                                      Examples
                      Typeset                                        Comment
                      V ˆ RI                                         RMS AC; or DC
                      V ˆ jXI                                        V and I are phasors
                                                                     X is a scalar (reactance)
                                                                     jX is an impedance (complex)
                      Z ˆ R ‡ jX                                     Z is complex (impedance)
                                                                     R is scalar (resistance)
                                                                     X is scalar (reactance)
                      u ˆ V m cos ot                                 u is an instantaneous value
                                                                     V m is a fixed scalar value





                         2.3   Basic source/load relationships
                      2.3.1   Fault level and circuit-breaker ratings

                      The fault level (sometimes called short-circuit level) is a term used to describe the
                      `strength' of a power supply: that is, its ability to provide both current and voltage. It
                      is defined as:

                             Fault level ˆ Open-circuit voltage   Short-circuit current [VA/phase]
                      The fault level provides a single number that can be used to select the size of circuit-
                      breaker needed at a particular point in a power system. Circuit-breakers must
                      interrupt fault currents (i.e. the current that flows if there is a short-circuit fault).
                      When the contacts of the circuit-breaker are separating, there is an arc which must be
                      extinguished (for example, by a blast of compressed air). The difficulty of extinguish-
                      ing the arc depends on both the current and the system voltage. So it is convenient to
                      take the product of these as a measure of the size or `power' of the circuit-breaker
                      that is needed. The fault level is used for this. The rating of a circuit-breaker should
   40   41   42   43   44   45   46   47   48   49   50