                                                             Power electronic control in electrical systems 39












                      Fig. 2.6 Development of the complexpower triangle.


                      S can be expressed graphically as the complex number P ‡ jQ, as shown in Figure
                      2.6, where

                        P is the real power in W, kW or MW, averaged over one cycle
                        Q is the reactive power in VAr, kVAr, or MVAr, also averaged over one
                        cycle 6
                        S ˆjSj is the apparent power or `volt±amperes', in VA, kVA or MVA 7
                      Let V be the reference phasor, and suppose that the load is inductive. Then


                                             I ˆ Ie  jf  ˆ I cos f   jI sin f             (2:3)

                      where f ˆ tan  1  (X/R) ˆ tan  1  (Q/P). The negative phase rotation  jf means that
                      the current lags behind the voltage. When we take the conjugate I and multiply by V

                      we get
                                           P ˆ VI cos f  and  Q ˆ VI sin f                (2:4)


                      Evidently P is positive and so is Q. A load that has positive reactive power is said to
                      `absorb' VArs. Inductive loads absorb VArs. Conversely, a capacitive load would
                      have

                                             I ˆ Ie ‡jf  ˆ I cos f ‡ jI sin f             (2:5)

                      In this case the current leads the voltage. P is still positive, but when we take the
                      conjugate I we get negative Q. We say that a capacitive load generates or supplies

                      VArs.
                        There is a distinction between the receiving end and the sending end. The expres-
                      sion `VI cos f' is correctly interpreted as power absorbed by the load at the receiving
                      end. But at the sending end the generated power P is supplied to the system, not
                      absorbed from it. The distinction is that the sending end is a source of power, while
                      the receiving end is a sink. In Figure 2.5, for example, both P s ˆ E s I cos f and
                                                                                         s

                      6
                       VAr ˆ `volt±amperes, reactive'
                      7
                       Although S is a complex number, it is not a phasor quantity. The power triangle merely represents the
                      relationship between P, Q,  , and the apparent power S. Note that P, Q, and S are all average quantities
                      (averaged over one cycle); they are not rms quantities. On the other hand V and I are rms quantities.