Page 52 - Power Electronic Control in Electrical Systems
P. 52

//SYS21/F:/PEC/REVISES_10-11-01/075065126-CH002.3D ± 42 ± [31±81/51] 17.11.2001 9:49AM







               42 Power systems engineering ± fundamental concepts










                      Fig. 2.10 Phasor diagram, capacitive load.


                        We can see from this that power-factor correction capacitors (connected in parallel
                      with an inductive load) will not only raise the power factor but will also increase the
                      voltage. On the other hand, if the voltage is too high, it can be reduced by connecting
                      inductors in parallel. In modern high-voltage power systems it is possible to control
                      the voltage by varying the amount of inductive or capacitive current drawn from the
                      system at the point where the voltage needs to be adjusted. This is called reactive
                      compensation or static VAR control. In small, isolated power systems (such as an
                      automotive or aircraft power system supplied from one or two generators) this is not
                      generally necessary because the open-circuit voltage of the generator E can be varied
                      by field control, using a voltage regulator.



                        2.6   Power factor correction

                      The load in Figure 2.7 can be expressed as an admittance Y ˆ G ‡ jB supplied from a
                      voltage V, where Y ˆ 1/Z. G is the conductance, i.e. the real part of the admittance Y,
                      and B is the susceptance, i.e. the reactive or imaginary part of the admittance Y. The
                      load current is I and for an inductive load the reactive component is negative
                      (equation (2.3)) so we can write
                                         I ˆ I R   jI X ˆ V(G   jB) ˆ VG   jVB           (2:8)
                      Both V and I are phasors, and equation (2.8) is represented in the phasor diagram
                      (Figure 2.11) in which V is the reference phasor. The voltage V and current I are in
                      common with Figure 2.9, but Figure 2.11 shows the components of the current I and
                      omits E and the voltage drop across the supply impedance. The load current has a
                      `resistive' or `real' component I R in phase with V, and a `reactive' or `imaginary'
                      component, I X ˆ VB in quadrature with V. The angle between V and I is f, the
                      power-factor angle. The apparent power supplied to the load is given by equation.
                                                                                           2
                                    2
                                                2
                      (2.2) with P ˆ V G and Q ˆ V B. For a capacitive load I X is positive and Q ˆ V B,
                      which is negative.
                        The real power P is usefully converted into heat, mechanical work, light, or other
                      forms of energy. The reactive volt±amperes Q cannot be converted into useful forms
                      of energy but is nevertheless an inherent requirement of the load. For example, in AC
                      induction motors it is associated with production of flux and is often called the
                      `magnetizing reactive power'.
                        The supply current exceeds the real component by the factor 1/ cos f, where cos f
                      is the power factor: that is, the ratio between the real power P and the apparent
                      power S. The power factor is that fraction of the apparent power which can be
   47   48   49   50   51   52   53   54   55   56   57