Page 62 - Power Electronic Control in Electrical Systems
P. 62

//SYS21/F:/PEC/REVISES_10-11-01/075065126-CH002.3D ± 52 ± [31±81/51] 17.11.2001 9:49AM







               52 Power systems engineering ± fundamental concepts













                      Fig. 2.19 Three-phase instantaneous and phasor currents.

                      This suggests that the circuit could be equally well served by the three-phase connec-
                      tion shown in Figure 2.20, which has only half the number of conductors compared
                      with Figure 2.18. Figure 2.20 also shows the cross-section of a three-phase cable
                      capable of carrying the required current. The total cross-section of conductor is 3 A,
                      that is a saving of 50%.
                        In the voltage phasor diagram in Figure 20, the voltage across each phase of the
                      load remains the same as in Figure 2.20, but the voltage between lines is increased:
                      evidently from the geometry of the triangles
                                                             p 
                                              V ab ˆ V a   V b ˆ  3Ve j30
                                                             p    j90
                                              V bc ˆ V b   V c ˆ  3Ve                   (2:24)
                                                             p   j150
                                              V ca ˆ V c   V a ˆ  3Ve
                      where V is the reference phase voltage taken as V a , measured between line A and the
                      `star point' of the load or the `neutral point' of the supply. Likewise the phase voltage
                      V b is measured between line B and the star-point of the load, and V c between line C
                                                                p
                      and the star point. The line±line voltages are  3 times the phase voltages. In
                      Figure 2.20 both the load and the generator are `wye connected' and in terms of
                      the RMS values only, we have
                                                   p 
                                            V LL ˆ  3V ph  and  I L ˆ I ph              (2:25)























                      Fig. 2.20 Three-phase connection with wye-connected load and phasor diagram.
   57   58   59   60   61   62   63   64   65   66   67