Page 139 - Power Electronics Handbook
P. 139

132   Power semiconductor protection
                          For clearance times which last over one cycle the fault current curves
                        must be kept below the rating of the power semiconductor, and even if the
                        fuse operates within one cycle the peak let-through current must be below
                        the ratin  of  the semiconductor. Fuses should also be designed with a low
                                9
                        ratio of i I to r.m.s. current rating. The r.m.s. current can be increased by
                        cooling the  fuse in  an  air stream, or by  mounting it on a  busbar or a
                        heatsink, the i2t characteristic not being affected by this. Fuses must also
                        have  a  sufficient  voltage-clearing capability,  otherwise  a  high-voltage
                        source can cause a  continuous arc under  fault conditions, with  loss of
                        protection. The arcing voltage should also be as low as possible to limit the
                        peak voltage which occurs across the circuit elements, but this is at the
                        expense of  the i2t characteristic.
                          The i2t of  a fuse is affected by circuit voltage and the prospective fault
                        current, as shown by the curves of Figure 5.10 for a particular fuse. As an
                        exercise into the use of  these characteristics suppose a fuse is needed to
                        protect  a  circuit operating at  300V and WA, the asymmetrical peak
                        current  being  13.5kVA.  Using  a  450V,  400A  r.m.s.  fuse,  whose
                        characteristics are shown in Figure 5.10, the normal i2t is 800000A’s  with
                        an asymmetrical peak current of 200kA. Figure 5.10(a) gives a reduced i2t
                        of 280000 at 300 V and drawing a line in Figure 5.10(b) passing through the
                        200kA, 280000A2s point, the value of  i2t at 13.5kVA is 150000. This is
                        now the rating of  the fuse under the circuit conditions described and it
                        should be less than that of the power semiconductors being protected. It is
                        possible to reduce the i2t of  the fuse by choosing one with a higher voltage
                        rating, but the excess of  fuse rating over supply voltage could give very
                        abrupt  arc  quenching  and  generate  high-voltage  transients.  A  better
                        method  of  reducing  the  fuse  i2t  is  to  decrease the  prospective  peak



                                 1   1   I   I  I,,  ,I  I
                              Maximum Operating values at:
                          0‘  - Rated voltage (450 V peak)
                              06% rated voltage
                              (300V peak)
                              (150V peak)
                        u)
                        U
                        8 104-



                       a
                         102 -





                                    Fuse rating (A)
                        (8)
                        FIpm 5.10 Variation of i2t with circuit voltage and prospective current for a typical 450V
                        400A r.m.s. fuse: (a) circuit voltage; (b) pmpective current
   134   135   136   137   138   139   140   141   142   143   144