114  Practical Power System and Protective Relays Commissioning











            FIGURE 10.9 Linear coupler current transformer.






















            FIGURE 10.10 Linear coupler current transformer (CT) versus normal CT.
            TPY Class
            These are CTs with antiremanence air gaps (remanence , 10%). Otherwise
            they behave the same as the TPX class.


            TPZ Class
            TPZ are CTs with a linear core (remanence may be neglected). The specified
            transformation accuracy only applies to the AC component while exponen-
            tially decaying DC is radically reduced.
               In summary:
               The IEC classification for TP of CTs as follows:
               TPS: Class X in British Standards
               TPX: Class P, no remanence limit
               TPY: Remanence less than 10% small air gap in core
               TPZ: Very low remanence and can be neglected

               A linear coupler air gap core with linear characteristics is shown in
            Fig. 10.9 and is discussed in the following section.
               In linear coupler V and I primary has a linear characteristic and are used in
            voltage balance differential relays used in BB protection.