Page 112 - Practical Power System and Protective Relays Commissioning
P. 112

110  Practical Power System and Protective Relays Commissioning



                    TABLE 10.2 Accuracy Versus Composite Error Calculations
                    Accuracy Class          Composite (%) Error
                    5P                      5
                    10P                     10


























            FIGURE 10.6 Typical excitation curve of multiratio 2000/5 Amp current transformer class X,
            V K 5 700 V, 60 Hz, R CT 5 0.85 Ω.

               Fig. 10.7 shows how to read the CT class for measuring and protection
            CTs.
               Let us look at an example: a CT classified as 5P10.
               The number 5 refers to the CT composite error in magnitude and angle.
               The number 10 refers to its ALF.
               This limit means a 6 5% error at 10 times of primary current.
                                          VA
                                     V K 5    : ALF
                                           IN
               Example:
               CT VA 5 15 VA 5P10
               ALF 5 10
                                       VA        15
                                  V K 5   :ALF 5   :10
                                       IN        1
                               2
               V K 5 150 V, VA 5 I .R
               Class 3 CT BS classified by:
               CT ratio, I m , R CT , V K , I P
   107   108   109   110   111   112   113   114   115   116   117