332  Practical Power System and Protective Relays Commissioning


            Subchapter 20.3


            Distance Protection Testing and
            Commissioning


            20.3.1 SECONDARY INJECTION TEST
            In this test we will inject voltage and current (fixed current) as per the manu-
            facturer’s test.
               Recommendation 1 or 2 A. For the Current Transformer (CT) with rated
            current of 1 A we decrease the voltage until we reach the zone reach for
            pH-E and pH pH characteristic for each phase R, Y, B and R-Y, Y-B, B-R
            phases as shown below:
            1. Relay data
               CT 5 2000/1 500 kV Transmission Line (TL)
               Phase-E characteristic Mho relay, pH pH characteristic, quadrilateral
            characteristic.
               Z 1 , Z 2 , Z 3 are given by relay setting engineer for pH-E and pH pH
            where:
               K 0 5 residual earth compensation factor.
                                             ðZ 0 2 Z L Þ
                                   K 0 5 0:6 5
                                               3Z L
               Z 1 5 positive-sequence impedance of TL
               Z 0 5 zero-sequence impedance of TL
                                           500; 000 100
                                 VT ratio 5       =
                                             O3    O3


                                       CT ratio     2000
                               Z s 5 Z p        5 Z p
                                       VT ratio     5000
               (Z s 5 Z p 0.4) and Z 3 reverse 5 0.25Z 1 5 5.25+ 260 degrees
               Z 1 5 21 Ω+80 degrees t 1 5 0
               Z 2 5 26 Ω+80 degrees t 2 5 500 ms
               Z 3 5 33 Ω +80 degrees t 3 5 1000 ms
               Z power swing 5 Z ps 5 1.3Z 3 5 42.9 +80 degrees blocking action after
            t 5 5 seconds.
               Fig 20.3.1 Relay characteristic for pH-E and pH pH.
            2. Pretest procedures:
               1. The current circuit of the CT secondary should be short-circuited if
                  the relay is to be tested in load condition.